Line No. Value
H1 function value (5954)
0
H1 voltage value 2 (5955)
10.0
H1 function value 2 (5956)
1000
(for equivalence
10 V = 100°C)
For a request via LPB
Check that the secondary regulator is defined for an LPB segment other
than 0 (reserved for generators)
Diagram: CX10
page 4 / 6
In all cases (LPB network menu)
Configure the boiler as master of the
cascade
Appliance address (6600)
1
Segment address (6601)
0
Bus supply function (6604)
Automatic
Clock operation (6640)
Master
On boiler(s) no. 2 (and above): slave
• Menu
Configuration
Configure the isolation valve Q1.2
Relay QX3 output (5892)
Boiler pump Q1
• Menu
LPB network
Configure the boiler as slave in the
cascade
Appliance address (6600)
2 (or above for
the other slaves)
Segment address (6601)
0
Bus supply function (6604)
Automatic
Clock operation (6640)
Slave without
adjustment
• Connect the bus between the boilers ( take care to respect the polarity).
•
Switch the slave boiler(s) off and on again. If communication is established properly, the clock
is updated correctly.
Warning
the boiler considers a heat demand for a voltage H1> 0.2 V and a resulting setpoint> 6 ° C *
The boiler no longer considers a heat demand for a voltage H1 <0.2V or a resulting setpoint <4 ° C *
In this second case, the boiler isolation valve will close. If the installation does not include a hydraulic
decoupling bottle, all the network pumps must be stopped at the risk of causing them to cavitate..
* : according to the scale entered in the parameter "5956"