G. OPTIMISING THE CONFIGURATION OF THE SLAVE BOILER (EQUIPPED
WITH THE B3000)
Cascade optimisation:
The cascade can be optimised as required using the parameters in the
Cascade
menu. See the
NAVISTEM B3000 boiler controller manual for more details.
Diagram: CX13
page 8 / 8
Maintenance optimisation:
It is possible to generate a maintenance message that does not cause a boiler fault. This maintenance
message can occur after the 3 following counters reach set values:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months
• Hours of burner operation (parameter 7040)
• Number of start-ups (parameter 7042)
The last 2 parameters depend on the boiler room's hydraulic installation. It is advisable to use
at least parameter 7044 for annual maintenance.
Line No. Value
Adjust the anti-legionella cycle temperature
setpoint
Anti-legionella setpoint (1645)
- - -
Adjust the duration of the anti-legionella cycle
Anti-legionella function duration
(1646)
- - -
• Menu
DHW tank
Adjust the primary rise/DHW
Rise in initial setpoint (5020)
- - -