84 / 116
00CNO0192-E (U0627512)
CONDENSINOX -
Installation, Use and Maintenance
On boiler no. 2: master
Line No. Value
• Menu
LPB network
Configure the boiler as master of the
cascade
Appliance address (6600)
Segment address (6601)
1
0
Bus supply function (6604)
Automatic
Clock operation (6640)
Slave without
adjustment
• Connect the bus between the boilers ( take care to respect the polarity).
•
Switch the slave boiler(s) off and on again. If communication is established properly, the clock is
updated correctly.
• Menu
Configuration
Configure the isolation valve Q1.2
Relay QX3 output (5892)
Boiler pump Q1
Diagram: CX13
page 5 / 8
E. ELECTRICAL AND HYDRAULIC VALIDATION
On boiler no. 1: slave
On the RVS 63
Line No. Value
• Menu
Input/output test
Check the outputs
DHW load pump (Q3)
Relay test (7700)
DHW pump Q3
Heating circuit 1 circulating pump (Q2)
Relay test (7700)
HC pump Q2
Opening of circuit 1 3-way valve (Y1)
Relay test (7700)
HC mixing valve
open Y1
Closing of circuit 1 3-way valve (Y2)
Relay test (7700)
HC mixing valve
close Y2
Heating circuit 2 pump (Q6)
Relay test (7700)
HC pump Q6
Opening of circuit 2 3-way valve (Y5)
Relay test (7700)
HC mixing valve
open Y5
Closing of circuit 2 3-way valve (Y6)
Relay test (7700)
HC mixing valve
close Y6
Reset the outputs
Relay test (7700)
No test