CONDENSINOX -
Installation, Use and Maintenance
9.4.
Specific configurations when connecting to 0-10V outputs (Ux)
9.4.1.
Transfer of the "burner power" image to PLC
IMPORTANT:
You cannot use this function if you are controlling a Q1 boiler pump with
one of the NAVISTEM B3000 0-10V outlets.
Parameter 9529
Parameter 9530
x 100
D. SPECIFIC START-UP PROCEDURE
Line No. Value
• Configuration
menu
Declare the output which gives the image
of the burner power.
Function output Ux (6078/6089)
Boiler pump Q1
Signal direction.
Progress of the 0-10V signal in the signal
increase direction for speed increase.
Signal logil output UX (6079/6090)
Standard
• Boiler
menu
Indication that the burner state is operating
at min
Output at pump speed min (2334)
0 %
Indication that the burner state is operating
at max
(parameters 9529 and 9530 may be viewed
in the
Burner control
menu)
Output at pump speed max (2335)
0-10V output state on start
Starting speed (2321)
between 0 and 100 %
0-10V output state when the burner is at min
Pump speed min (2322)
between 0 and 100 %
0-10V output state when the burner is at
max
Pump speed max (2323)
between 0 and 100 %
burner
boiler
Load rate image