AIR-TO-WATER HEAT PUMP PRODUCT
5
4 PRODUCT DATA
4.1 Product Data at Rated Condition
4.1.1 Outdoor
AIR TO WATER HEAT PUMP
Model
GRS-CQ
6.0Pd/N
a-K(O)
GRS-CQ
8.0Pd/Na-
K(O)
GRS-CQ
10Pd/Na-
K(O)
GRS-CQ
12Pd/Na
-K(O)
GRS-CQ
14Pd/Na-
K(O)
Heating(floor heating)
kW
6.2
8.5 10 12 14
Capacity
1
Cooling(floor cooling)
kW
5.5
9.0 10.5 14 15
Heating(floor heating)
kW
1.5
2.10 2.50 2.67 3.33
Power
Input
1
Cooling(floor cooling)
kW
1.6
2.50 3.14 3.68 4.28
EER
1
Cooling(floor cooling)
-
3.4
3.60 3.35 3.8 3.5
COP
1
Heating(floor heating)
-
4.1
4.00 4.00 4.5 4.20
Heating(Fan coil or
Radiator)
kW
5.5
8.0 9.0 11.5 13
Capacity
2
Cooling(for Fan coil)
kW
4
6.5 8.0 10 11
Heating(Fan coil or
Radiator)
kW
1.8 2.65
2.90 3.35 3.88
Power
Input
2
Cooling(for Fan coil)
kW
1.53
2.50 3.08 3.45 3.93
EER
2
Cooling(for Fan coil)
-
2.6
2.6 2.6 2.9 2.80
COP
2
Heating(Fan coil or
Radiator)
-
3.0 3.0
3.1 3.40 3.35
Type -
R410A
R410A R410A R410A R410A
Refrigerant
Charge g
1700
2000 2000 3300 3300
Sanitary water Temperature
℃
40-80
40-80
40-80
40-80
40-80
Sound Pressure Level
dB(A)
59
59 59 59 59
Gas Piping Connection
mm
12.7
15.9 15.9 15.9 15.9
Liquid Piping Connection
mm
6.35
9.52 9.52 9.52 9.52
Dimensions
Outdoor
unit
W×D×H
(unpacked)
mm
921×
427×791
921×
427×791
921×427
×791
950×412
×1253
950×412
×1253
Summary of Contents for SXVD200LCJ/A-K
Page 1: ...Air to Water Heat Pump Service Manual T1 R410A 50Hz GREE ELECTRIC APPLIANCES INC OF ZHUHAI...
Page 3: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP PRODUCT...
Page 15: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP CONTROL...
Page 69: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP INSTALLATION...
Page 81: ...AIR TO WATER HEAT PUMP INSTALLATION 76...
Page 107: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP MAINTENANCE...
Page 117: ...AIR TO WATERHEATPUMP MAINTENANCE 111 6 Temperature sensor error 7 Communication Malfunction E6...
Page 121: ...AIR TO WATERHEATPUMP MAINTENANCE 115 3 1 3 Trip Fig 3 1 3 Flowchart of trip diagnosis...
Page 148: ...AIR TO WATERHEATPUMP MAINTENANCE 142 Indoor Unit 1 Front panel assy Fig 2 Fig 1 Fig 2...
Page 153: ...AIR TO WATERHEATPUMP MAINTENANCE 147 Exploded View of GRS CQ8 0Pd Na k O and GRS CQ10Pd Na K O...