AIR-TO-WATER HEAT PUMP CONTROL
12
UNITS CONTROL
1 OPERATION FLOWCHART
2 MAIN LOGIC
2.1 Defrosting Mode
2.1.1 The condition of start defrosting mode:
Under heating mode or water heating mode, if the accumulative running time of
compressor is over the set interval time of defrosting
(
default 50min
),
and the defrosting
temperature(outdoor unit heat exchanger temperature) is lower than the set starting
temperature(default -4
℃
) ,the unit will start running defrosting, and the 4-way valve will
shut off and the outdoor fan will stop