AIR-TO-WATERHEATPUMP MAINTENANCE
113
3.1 Diagnosis Flowchart of Driving of Single-phase Unit
3.1.1 PFC Abnormality
Fig. 3.1.1
Flowchart of diagnosis of PFC abnormality
3.1.2 IPM Protection
The reasons may be:
●
Untight screws of IPM module
●
damaged IPM module
●
defective radiating of IPM module
●
ab15V power strip
●
abnormal PFC module