AIR-TO-WATER HEAT PUMP INSTALLATION
98
(1) : Normal Open type. When electric power is NOT supplied, the valve is open. (When electric
power is supplied, the valve is closed.)
(2) : Normal Closed type. When electric power is NOT supplied, the valve is closed. (When electric
power is supplied, the valve is open.)
How to Wire 2-Way Valve
Follow below procedures Step 1 ~ Step 2.
Step 1. Uncover front cover of the indoor unit and open the control box.
Step 2. Find terminal block and connect wire as below.
3
2
1
2 way value 1
2 way value 2
4
5
6
OFF
ON
N
OFF
ON
N
NC
NO
N
N
NC
NO
• Normal Open type should be connected to wire (NO) and wire (N)for valve closing in cooling mode.
• Normal Closed type should be connected to wire (NC) and wire (N)for valve closing in cooling mod
(NO) : Line signal (for Normal Open type) from PCB to 2way valve
(NC) : Line signal (for Normal Closed type) from PCB to 2way valve
(N) : Neutral signal from PCB to 2way valve
2.3.8 3-Way Valve
3way valve is required to operate sanitary water tank. Role of 3way valve is flow
switching between under floor heating loop and water tank heating loop.
General Information
Type Power Operating
Mode Supported
Selecting “Flow A” between
“Flow A” and “Flow B”
Yes
SPDT
3-wire
230V 50Hz
~
AC
Selecting “Flow B” between
“Flow B” and “Flow A”
Yes
(1) : SPDT = Single Pole Double Throw. Three wires consist of Live1 (for selecting (for selecting
Flow B), and Neutral (for common).
(2) : Flow A means ‘water flow from the indoor unit to under floor water circuit.’
(3) : Flow B means ‘water flow from the indoor unit to sanitary water tank.’
How to Wire 3Way Valve
Follow below procedures Step 1 ~ Step 2.
Step 1. Uncover front cover of the indoor unit and open the control box.
Step 2. Find terminal block and connect wire as below.
Summary of Contents for SXVD200LCJ/A-K
Page 1: ...Air to Water Heat Pump Service Manual T1 R410A 50Hz GREE ELECTRIC APPLIANCES INC OF ZHUHAI...
Page 3: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP PRODUCT...
Page 15: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP CONTROL...
Page 69: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP INSTALLATION...
Page 81: ...AIR TO WATER HEAT PUMP INSTALLATION 76...
Page 107: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP MAINTENANCE...
Page 117: ...AIR TO WATERHEATPUMP MAINTENANCE 111 6 Temperature sensor error 7 Communication Malfunction E6...
Page 121: ...AIR TO WATERHEATPUMP MAINTENANCE 115 3 1 3 Trip Fig 3 1 3 Flowchart of trip diagnosis...
Page 148: ...AIR TO WATERHEATPUMP MAINTENANCE 142 Indoor Unit 1 Front panel assy Fig 2 Fig 1 Fig 2...
Page 153: ...AIR TO WATERHEATPUMP MAINTENANCE 147 Exploded View of GRS CQ8 0Pd Na k O and GRS CQ10Pd Na K O...