AIR-TO-WATERHEATPUMP MAINTENANCE
104
communication line are not
mounted with magnetic ring.
z
The outdoor unit is not
electrically powered
Fc
High pressure sensor
error
z
The sensor is damaged.
z
The wire of the sensor is loose.
z
The position of the sensor is
wrong
It will be automatically cleared
after the failure is removed.
F9
Outlet temperature
sensor error
z
The plug on temperature
sensor is not correctly
connected to the socket on
mainboard.
z
The resistance of temperature
sensor is not correct.
It will be automatically cleared
after the failure is removed.
dH
Backup outlet
temperature sensor error
z
The plug on temperature
sensor is not correctly
connected to the socket on
mainboard.
z
The resistance of temperature
sensor is not correct.
It will be automatically cleared
after the failure is removed.
F1
Lliquid pipe temperature
sensor Inside refrigerant
error
z
The plug on temperature
sensor is not correctly
connected to the socket on
mainboard.
z
The resistance of temperature
sensor is not correct.
It will be automatically cleared
after the failure is removed.
F8
Inlet temperature sensor
error
z
The plug on temperature
sensor is not correctly
connected to the socket on
mainboard.
z
The resistance of temperature
sensor is not correct.
It will be automatically cleared
after the failure is removed.
FE
The second sanitary
water tank temperature
sensor error
z
The plug on temperature
sensor is not correctly
connected to the socket on
mainboard.
z
The resistance of temperature
sensor is not correct.
It will be automatically cleared
after the failure is removed.
FL
The first sanitary water
tank temperature sensor
error
z
The plug on temperature
sensor is not correctly
connected to the socket on
mainboard.
z
The resistance of temperature
It will be automatically cleared
after the failure is removed.
Summary of Contents for SXVD200LCJ/A-K
Page 1: ...Air to Water Heat Pump Service Manual T1 R410A 50Hz GREE ELECTRIC APPLIANCES INC OF ZHUHAI...
Page 3: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP PRODUCT...
Page 15: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP CONTROL...
Page 69: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP INSTALLATION...
Page 81: ...AIR TO WATER HEAT PUMP INSTALLATION 76...
Page 107: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP MAINTENANCE...
Page 117: ...AIR TO WATERHEATPUMP MAINTENANCE 111 6 Temperature sensor error 7 Communication Malfunction E6...
Page 121: ...AIR TO WATERHEATPUMP MAINTENANCE 115 3 1 3 Trip Fig 3 1 3 Flowchart of trip diagnosis...
Page 148: ...AIR TO WATERHEATPUMP MAINTENANCE 142 Indoor Unit 1 Front panel assy Fig 2 Fig 1 Fig 2...
Page 153: ...AIR TO WATERHEATPUMP MAINTENANCE 147 Exploded View of GRS CQ8 0Pd Na k O and GRS CQ10Pd Na K O...