AIR-TO-WATER HEAT PUMP CONTROL
54
Step 2: Set timing temperature of the first period
1) The last timing temperature of the first period is defaulted. (The defaulted time is 8
:
00 upon initial energization. If the reference point is indoor temperature, the defaulted
temperature is 20 for cooling and 26 for heating. If the reference point is outflow
℃
℃
water temperature, the defaulted temperature is 18 for cooling and 40 for
℃
℃
heating.) Press “
▲
” and “
▼
” button to adjust starting hour. Press “Set” to save the
adjustment;