AIR-TO-WATER HEAT PUMP PRODUCT
6
AIR TO WATER HEAT PUMP
Model
GRS-CQ12P
d/Na-M(O)
GRS-CQ14P
d/Na-M(O)
GRS-CQ16P
d/Na-M(O)
GRS-CQ16P
d/Na-K(O)
Heating(floor heating)
kW
12 14 15
16
Capacity
1
Cooling(floor cooling)
kW
14 15 15.5
15.5
Heating(floor heating)
kW
2.8 3.33 3.9
3.90
Power
Input
1
Cooling(floor cooling)
kW
3.8 4.28 4.4
4.62
EER
1
Cooling(floor cooling)
-
3.8 3.5 3.5
3.35
COP
1
Heating(floor heating)
-
4.5 4.2 4
4.00
Heating(Fan coil or
Radiator)
kW
11 12 14
14
Capacity
2
Cooling(for Fan coil)
kW
10 10.5 11
11.5
Heating(Fan coil or
Radiator)
kW
3.35 3.8 4.2
4.59
Power
Input
2
Cooling(for Fan coil)
kW
3.45 3.6 4
4.20
EER
2
Cooling(for Fan coil)
-
2.9 2.8 2.7
2.50
COP
2
Heating(Fan coil or
Radiator)
-
3.4 3.35 3.2
3.05
Type -
R410A R410A R410A
R410A
Refrigerant
Charge g
3500 3500 3500
3300
Sanitary water Temperature
℃
40-80 40-80
40-80
40-80
Sound Pressure Level
dB(A)
59 59 62
62
Gas Piping Connection
mm
15.9 15.9 15.9
15.9
Liquid Piping Connection
mm
9.52 9.52 9.52
9.52
Dimens
io
ns
Outdoor
unit
W×D×H
(unpacked)
mm
950×412×
1253
950×412×
1253
950×412×
1253
950×412×
1253
Note :
1
Capacities and power inputs are based on the following conditions:
①
.Cooling conditions –
Indoor Water Temperature 23°C/18°C;
Outdoor Air Temperature 35°CDB/24°CWB
②
.Heating conditions
Indoor Water Temperature 30°C/35°C;
Outdoor Air Temperature 7°CDB/6°CWB
③
.Standard piping length 7.5m
2
Capacities and power inputs are based on the following conditions:
①
.Cooling conditions
Indoor Water Temperature 12°C/7°C;
Outdoor Air Temperature 35°CDB/24°CWB
②
.Heating conditions –
Indoor Water Temperature 40°C/45°C;
Outdoor Air Temperature 7°CDB/6°CWB
③
Standard piping length 7.5m
Summary of Contents for SXVD200LCJ/A-K
Page 1: ...Air to Water Heat Pump Service Manual T1 R410A 50Hz GREE ELECTRIC APPLIANCES INC OF ZHUHAI...
Page 3: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP PRODUCT...
Page 15: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP CONTROL...
Page 69: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP INSTALLATION...
Page 81: ...AIR TO WATER HEAT PUMP INSTALLATION 76...
Page 107: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP MAINTENANCE...
Page 117: ...AIR TO WATERHEATPUMP MAINTENANCE 111 6 Temperature sensor error 7 Communication Malfunction E6...
Page 121: ...AIR TO WATERHEATPUMP MAINTENANCE 115 3 1 3 Trip Fig 3 1 3 Flowchart of trip diagnosis...
Page 148: ...AIR TO WATERHEATPUMP MAINTENANCE 142 Indoor Unit 1 Front panel assy Fig 2 Fig 1 Fig 2...
Page 153: ...AIR TO WATERHEATPUMP MAINTENANCE 147 Exploded View of GRS CQ8 0Pd Na k O and GRS CQ10Pd Na K O...