AIR-TO-WATERHEATPUMP MAINTENANCE
105
sensor is not correct.
F3
Gas pipe temperature
sensor inside refrigerant
error
z
The plug on temperature
sensor is not correctly
connected to the socket on
mainboard.
z
The resistance of temperature
sensor is not correct.
It will be automatically cleared
after the failure is removed.
dF
other thermal outlet
temperature sensor error
z
The plug on temperature
sensor is not correctly
connected to the socket on
mainboard.
z
The resistance of temperature
sensor is not correct.
It will be automatically cleared
after the failure is removed.
F0
Remote room
temperature sensor error
z
The plug on temperature
sensor is not correctly
connected to the socket on
mainboard.
z
The resistance of temperature
sensor is not correct.
It will be automatically cleared
after the failure is removed.
Ec
Water switch error
z
The switch is damaged.
z
The wire of the switch is loose.
z
The position of the switch is
wrong
It will be cleared after the
unit is turned off.
E2
Indoor anti-frozen
protetion
z
The resistance of temperature
sensor is not correct.
z
The electric expansion valve
can not work normally.
It will be cleared once
malfunction is removed or it
will be shown all the time; but
it will be cleared immediately
when switching operation
mode.
No display
Sanitary water tank
High-temp protection
z
The resistance of temperature
sensor is not correct.
z
The plug on temperature
sensor is not correctly
connected to the socket on
mainboard.
z
Mainboard of outdoor unit is
damaged.
Press ON/OFF key to clear
Ed
outlet temperature
High-temp protection
(This error code will not
displayed on wired
controller but only on
mainboard of outdoor unit)
z
The resistance of temperature
sensor is not correct.
z
The plug on temperature
sensor is not correctly
connected to the socket on
mainboard.
De-energize the unit and then,
energize it again. If the
malfunction is removed, the
code will be cleared.
Summary of Contents for SXVD200LCJ/A-K
Page 1: ...Air to Water Heat Pump Service Manual T1 R410A 50Hz GREE ELECTRIC APPLIANCES INC OF ZHUHAI...
Page 3: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP PRODUCT...
Page 15: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP CONTROL...
Page 69: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP INSTALLATION...
Page 81: ...AIR TO WATER HEAT PUMP INSTALLATION 76...
Page 107: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP MAINTENANCE...
Page 117: ...AIR TO WATERHEATPUMP MAINTENANCE 111 6 Temperature sensor error 7 Communication Malfunction E6...
Page 121: ...AIR TO WATERHEATPUMP MAINTENANCE 115 3 1 3 Trip Fig 3 1 3 Flowchart of trip diagnosis...
Page 148: ...AIR TO WATERHEATPUMP MAINTENANCE 142 Indoor Unit 1 Front panel assy Fig 2 Fig 1 Fig 2...
Page 153: ...AIR TO WATERHEATPUMP MAINTENANCE 147 Exploded View of GRS CQ8 0Pd Na k O and GRS CQ10Pd Na K O...