AIR-TO-WATER HEAT PUMP INSTALLATION
73
SXVD200LCJ/A-K
SXVD200LCJ2/A-K
SXVD300LCJ/A-K SXVD300LCJ2/A-K
SXVD200LCJ/A-M
SXVD200LCJ2/A-M
SXVD300LCJ/A-M SXVD300LCJ2/A-M
Litre
200L 200L 300L 300L
coil
specification
SUS304
Ф
22X0.8
M
\ 10m \ 10m
coil
length
N
13m 13m 18.5m
18.5m
D(mm)
540 620
D1(mm)
438 528
H(mm)
1595 1620
A(mm)
272 280
B(mm)
105
C(mm)
112
E(mm)
432 464
F(mm)
431 399
I(mm)
\ 80 \ 95
J(mm)
\ 247.5 \ 202.5
K(mm)
739 718
Outline
(Diameter×H)
(mm)
Φ
540X1595
Φ
620X1620
Package
(W*D*H)
(mm)
1620X625X630 1645X705X710
Net
weight
kg
68 71 82 87
Gross
weight
kg
77 80 92 97
Connection of Waterway System
If connection between water tank and indoor unit should be through the wall, drill a
hole
φ
70 for pass of circulating water pipe. It is unnecessary if the hole is not needed.
Preparation of pipelines:
Circulating water outlet/inlet pipe must be hot water pipe,
PPR pipe with nominal out diameter of dn25 and S2.5 series (wall thickness of 4.2mm)
being recommended. Cooling water inlet pipe and hot water outlet pipe of water tank
should also be hot water pipe, PPR pipe with nominal out diameter of dn20 and S2.5
series (wall thickness of 3.4mm) being recommended. If other insulated pipes are
adopted, refer to the above dimensions for out diameter and wall thickness.
Installation of circulating water inlet/outlet pipes:
Connect the water inlet of unit
with circulating outlet of water tank and water outlet of unit with circulating inlet of
water tank.
Installation of water inlet/outlet pipes of water tank:
Safety check valve (
→
on the
valve body points at water tank), filter and cut-off valve must be installed for water
inlet pipe according to the installation sketch of unit. At least a cut-off valve is needed
for the water outlet pipe.
Installation of blow-off pipe at the bottom of water tank:
Connect a piece of PPR
pipe with drainage outlet to floor drain. A cut-off valve must be installed in the middle
of the drainage pipe and at the place where it is easy to be operated by the users.
Summary of Contents for SXVD200LCJ/A-K
Page 1: ...Air to Water Heat Pump Service Manual T1 R410A 50Hz GREE ELECTRIC APPLIANCES INC OF ZHUHAI...
Page 3: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP PRODUCT...
Page 15: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP CONTROL...
Page 69: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP INSTALLATION...
Page 81: ...AIR TO WATER HEAT PUMP INSTALLATION 76...
Page 107: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP MAINTENANCE...
Page 117: ...AIR TO WATERHEATPUMP MAINTENANCE 111 6 Temperature sensor error 7 Communication Malfunction E6...
Page 121: ...AIR TO WATERHEATPUMP MAINTENANCE 115 3 1 3 Trip Fig 3 1 3 Flowchart of trip diagnosis...
Page 148: ...AIR TO WATERHEATPUMP MAINTENANCE 142 Indoor Unit 1 Front panel assy Fig 2 Fig 1 Fig 2...
Page 153: ...AIR TO WATERHEATPUMP MAINTENANCE 147 Exploded View of GRS CQ8 0Pd Na k O and GRS CQ10Pd Na K O...