AIR-TO-WATER HEAT PUMP PRODUCT
8
INDOOR UNIT
Model
GRS-CQ16P
d/Na-K(I)
GRS-CQ12P
d/Na-M(I)
GRS-CQ14
Pd/Na-M(I)
GRS-CQ16
Pd/Na-M(I)
Power Supply
V /
Ph
/Hz
220
~
240V/1Ph/50
Hz
380
~
415V/3Ph/50Hz
Rated
input (indoor only)
W
6200
Liquid side diameter
mm(in
ch)
9.52(3/8)
Gas side diameter
mm(in
ch)
15.9(5/8)
Cooling (FCU)
℃
7-25
Cooling (Floor )
℃
18-25
Heating (FCU)
℃
25-55(High Temperature Cycle)
Operation
Range(Outflow
water temp.)
Heating (Floor )
℃
25-45 (Low Temperature Cycle)
Type -
Water-cooled
Nr. of speed
-
3
Power input
W
200
pump
Water flow
limit
LPM
7.5
Volume Liter
10
Water Pressure
(Max)
Bar
3
Expansion
Vessel
Water Pressure
(Pre)
Bar
1
Type -
Sheath
Material -
Stainless Steel
Operation -
Automatic
Steps - 2
1
Capacity
Combination
KW
3+3
6
Electric
Heater
Power input
Ph
/V/Hz
1/230/50
3/400/50
Type -
Brazed Plate HEX
Ma
in
co
mp
onen
ts
Heat
Exchanger
Quantity -
1
Unit(W×D× H)
mm
900
×
500
×
324
Dimens
io
ns
Packed unit(W×D× H)
mm
1040
×
605
×
380
Summary of Contents for SXVD200LCJ/A-K
Page 1: ...Air to Water Heat Pump Service Manual T1 R410A 50Hz GREE ELECTRIC APPLIANCES INC OF ZHUHAI...
Page 3: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP PRODUCT...
Page 15: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP CONTROL...
Page 69: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP INSTALLATION...
Page 81: ...AIR TO WATER HEAT PUMP INSTALLATION 76...
Page 107: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP MAINTENANCE...
Page 117: ...AIR TO WATERHEATPUMP MAINTENANCE 111 6 Temperature sensor error 7 Communication Malfunction E6...
Page 121: ...AIR TO WATERHEATPUMP MAINTENANCE 115 3 1 3 Trip Fig 3 1 3 Flowchart of trip diagnosis...
Page 148: ...AIR TO WATERHEATPUMP MAINTENANCE 142 Indoor Unit 1 Front panel assy Fig 2 Fig 1 Fig 2...
Page 153: ...AIR TO WATERHEATPUMP MAINTENANCE 147 Exploded View of GRS CQ8 0Pd Na k O and GRS CQ10Pd Na K O...