AIR-TO-WATERHEATPUMP MAINTENANCE
103
E1
Comp High-pressure
protection
z
Comp High-pressure switch is
broken or the wiring is loose.
z
The water in the tank is not
enough.
z
The installation of tank temp
sensor is not correct.
z
The gas valve and liquid valve
are not fully open.
z
The electric expansion valve
can not work normally.
De-energize the unit and then,
energize it again. If the
malfunction is removed, the
code will be cleared.
E3
Comp Low- pressure
protection
z
Comp Low-pressure switch is
broken or the wiring is loose.
z
The system has leaked.
z
The fans stop running or
reverse.
It will be cleared if the
malfunction is removed after
the unit has been turned off.
E4
Comp Discharge temp
protection
z
The resistance of temperature
sensor is not correct.
z
The electric expansion valve is
blocked.
z
The system has leaked.
z
Mainboard of outdoor unit is
damaged.
It will be cleared if the
discharge temp is lower than
92
℃
.
C5
Indoor capacity switch
error
De-energize the unit and then,
energize it again. If the
malfunction is removed, the
code will be cleared.
E6
Communication
malfunction
(
between
outdoor and indoor
mainboard
)
z
The communication line of the
unit is not connected.
z
The communication line is not
through.
z
The communication line of the
unit is not connected correctly.
z
The two ends of
communication line are not
mounted with magnetic ring.
z
The outdoor unit is not
electrically powered
It will be cleared once
communication recovers or it
will be shown all the time
E6
Communication
malfunction
(
between
outdoor mainboard and
wired controller
)
z
The communication line of the
unit is not connected.
z
The communication line is not
through.
z
The communication line of the
unit is not connected correctly.
z
The two ends of
It will be cleared once
communication recovers or it
will be shown all the time
Summary of Contents for SXVD200LCJ/A-K
Page 1: ...Air to Water Heat Pump Service Manual T1 R410A 50Hz GREE ELECTRIC APPLIANCES INC OF ZHUHAI...
Page 3: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP PRODUCT...
Page 15: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP CONTROL...
Page 69: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP INSTALLATION...
Page 81: ...AIR TO WATER HEAT PUMP INSTALLATION 76...
Page 107: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP MAINTENANCE...
Page 117: ...AIR TO WATERHEATPUMP MAINTENANCE 111 6 Temperature sensor error 7 Communication Malfunction E6...
Page 121: ...AIR TO WATERHEATPUMP MAINTENANCE 115 3 1 3 Trip Fig 3 1 3 Flowchart of trip diagnosis...
Page 148: ...AIR TO WATERHEATPUMP MAINTENANCE 142 Indoor Unit 1 Front panel assy Fig 2 Fig 1 Fig 2...
Page 153: ...AIR TO WATERHEATPUMP MAINTENANCE 147 Exploded View of GRS CQ8 0Pd Na k O and GRS CQ10Pd Na K O...