AIR-TO-WATER HEAT PUMP CONTROL
22
Table of user function parameter
Code Function
description
Detail
Range
1
Setting temperature selection:
Selection for setting temperature as
room temperature or outflow water
temperature
0: leaving water
temperature
1: room temperature
0~1(default: 0)
2 Forced
Operation
0: no Forced operation
1: Forced cooling
operation
2: Forced heating
operation
0~2(default: 0)
3
Celsius/Fahrenheit switching:
Display temperature in Celsius or
Fahrenheit
0:Celsius
1:Fahrenheit
0~1(default: 0)
4
Thermostat control isEnable/disable
0: disable
1: enable
0~1(default: 0)
5
Enable/disable of quick sanitary heating
0: disable
1: enable
0~1(default: 0)
6
Enable/disable of disinfection operation
0: disable
1: enable
0~1(default: 0)
7
Enable/disable of holiday mode
0: disable
1: enable
0~1(default: 0)
8
Setting priority when under cooling
demand and sanitary water heating
demand are required at the same time
0: priority to cooling
1: priority to water tank
heating
0~1(default: 0)
9
Setting priority when under heating
demand and sanitary water heating
demand are required at the same time
0: priority to heating
1: priority to water tank
heating
0~1(default: 0)
10
Setting status of back-up heater(indoor
unit)
1: use half capacity of
Back-up heater(3kW)
2: use full capacity of
Back-up heater(6kW)
1~2(default:
1
)
11
Setting start date of disinfection
operation
0: Sunday
1: Monday
2: Tuesday
3: Wednesday,
4: Thursday
5: Friday
6: Saturday
0~6(default: 6)
12
Setting start time in 24 hours of
disinfection operation
00-00
:
00
01-01
:
00
…
23-23:00
0~23(default:23)
13
Enable/disable of Metal Base
(pedestal)heater
0: disable
1: enable
0~1(default:1)
14
Tank sensor quantity
1: one
2: two
1~2(default:2)
15 Tank
equipment
0: NOT Equipped
1: Equipped
0~1(default: 0)
16 Other
thermal
equipment
0: NOT Equipped
1: Equipped
0~1(default: 0)
17 FCU
equipment
0: NOT Equipped
1: Equipped
0~1(default: 0)
18
Remote air temperature sensor
0: NOT Equipped
1: Equipped
0~1(default: 0)
19
Heating operation level
0: high temperature cycle
1: low temperature cycle
0~1(default:1)
Summary of Contents for SXVD200LCJ/A-K
Page 1: ...Air to Water Heat Pump Service Manual T1 R410A 50Hz GREE ELECTRIC APPLIANCES INC OF ZHUHAI...
Page 3: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP PRODUCT...
Page 15: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP CONTROL...
Page 69: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP INSTALLATION...
Page 81: ...AIR TO WATER HEAT PUMP INSTALLATION 76...
Page 107: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP MAINTENANCE...
Page 117: ...AIR TO WATERHEATPUMP MAINTENANCE 111 6 Temperature sensor error 7 Communication Malfunction E6...
Page 121: ...AIR TO WATERHEATPUMP MAINTENANCE 115 3 1 3 Trip Fig 3 1 3 Flowchart of trip diagnosis...
Page 148: ...AIR TO WATERHEATPUMP MAINTENANCE 142 Indoor Unit 1 Front panel assy Fig 2 Fig 1 Fig 2...
Page 153: ...AIR TO WATERHEATPUMP MAINTENANCE 147 Exploded View of GRS CQ8 0Pd Na k O and GRS CQ10Pd Na K O...