AIR-TO-WATER HEAT PUMP CONTROL
27
25 to 55 . The high temperature cycle suitable for FCU or radiator is equipped
℃
℃
in the water loop.
If
code 19 is set as 1, in space heating
,
the unit will be operated by low temperature
cycle. The setting value of outflow water temperature ranges from 25 to 45
℃
℃
,
low temperature cycle suitable for under-floor coil is equipped in the water loop.
z
Function code 20
:
Setting startup temperature of back-up heater
(
indoor
unit
)
Set the outdoor air temperature when half capacity of electric heater starts
operating.
Example
: If Value is set as ‘-1’
:
Half capacity of electric heater will start operating when outdoor air temperature is
below -1°… and current outflow water temperature or room air temperature is much
lower than target outflow water temperature or target room air temperature.
z
Function code 21
:
Setting maximum water tank temperature heated by heat
pump cycle
Set the maximum temperature generated by AWHP compressor cycle.
Example
: If Value is set as ‘50’
:
If the target water tank temperature is 60 , and when the current water tank
℃
temperature is below 50 , the water tank is heated by heat pump. When current
℃
water tank temperature is higher than 50 but lower than target
℃
water tank
temperature (in this case is 60 ), the water tank is heated by water heater in tank
℃
z
Function code 22
:
Setting heating temperature of disinfection operation
Set the target temperature of disinfection operation.
Disinfection operation is special sanitary tank operation mode to kill and to prevent
growth of viruses inside the tank.
Before set this function, the value of code 6 should be set as 1.
z
Function code 23, 24: Setting the range of weather-dependent operation
Weather-dependent operation is that the unit automatically adjusts target
temperature (outflow water or room air) according to the outdoor air temperature.
Value of code 23:
Lower limit of the outdoor air temperature;
Value of code 24:
Upper limit of the outdoor air temperature;
z
Function code 25: Setting temperature gap from target temperature of
cooling operation
Set the
temperature gap from target temperature (outflow water or room air) in
Summary of Contents for SXVD200LCJ/A-K
Page 1: ...Air to Water Heat Pump Service Manual T1 R410A 50Hz GREE ELECTRIC APPLIANCES INC OF ZHUHAI...
Page 3: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP PRODUCT...
Page 15: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP CONTROL...
Page 69: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP INSTALLATION...
Page 81: ...AIR TO WATER HEAT PUMP INSTALLATION 76...
Page 107: ...GREE COMMERCIAL AIR CONDITIONERS AIR TO WATER HEAT PUMP MAINTENANCE...
Page 117: ...AIR TO WATERHEATPUMP MAINTENANCE 111 6 Temperature sensor error 7 Communication Malfunction E6...
Page 121: ...AIR TO WATERHEATPUMP MAINTENANCE 115 3 1 3 Trip Fig 3 1 3 Flowchart of trip diagnosis...
Page 148: ...AIR TO WATERHEATPUMP MAINTENANCE 142 Indoor Unit 1 Front panel assy Fig 2 Fig 1 Fig 2...
Page 153: ...AIR TO WATERHEATPUMP MAINTENANCE 147 Exploded View of GRS CQ8 0Pd Na k O and GRS CQ10Pd Na K O...