GE-NUTRI USER’S GUIDE
GE-NUTRI
Section C-65
5.
This parameter is used to set the potentiometer lower limit for the actuator
calibration. This will effectively define the lowest possible value for the
actuator’s potentiometer. To obtain this value, completely close the actuator
using
OPER MANUAL [4]
. Once the actuator is completely closed, press
SELECT
when the cursor is on this parameter. At this point, the text displayed
here will change to
"Low Limit Saved"
if the value was correctly saved,
"Can’t Save Check Pot"
if the value of the potentiometer could not be
read or
"Can’t Save Low Limit"
if an error occurred during the
operation. In the two later cases, calibration must be performed once the
situation is corrected.
6.
This parameter is used to set the potentiometer upper limit for calibration of
the actuator. This will effectively define the highest value that can be read by
the actuator potentiometer. To get this value, completely open the actuator
using
OPER MANUAL [4]
. Once the actuator is completely open, press
SELECT
when the cursor is on this setting. At this point, the text displayed
here will change to
"High Limit Saved"
if the value was correctly saved,
"Can’t Save Check Pot"
if the value of the potentiometer could not be
read or
"Can’t Save Hi Limit"
if an error occurred during the
operation. In the two later cases, calibration must be performed once the
situation is corrected.
7.
This parameter is used to set the maximum run time of the actuator within a
ten-minute period. When an actuator has moved for a time greater than the
value of this parameter within a ten-minute period, the module will not
activate the open or close relays until the actuator has had time to cool down
and an alarm message will be logged in the alarm history. The alarm goes off
if the
ACTUATOR ALARM [3]
is set to
"ON"
. This value should be set
according to the manufacturer’s specifications. Setting this value to “
OFF
” will
deactivate the module cool down function. If the actuator is already in cool
down mode when this parameter is set to “
OFF
”, it will finish the cool down
period before deactivating the function. This parameter is adjusted in 1-
minute increments from 1 minute to 9 minutes, “
OFF
”.
Summary of Contents for GE-NUTRI
Page 3: ...GE NUTRI WIRING DIAGRAM GE NUTRI Section A 3 WIRING DIAGRAM GE NUTRI SECTION A...
Page 10: ...GE NUTRI INSTALLATION Section B 10 GE NUTRI INSTALLATION GE NUTRI SECTION B...
Page 21: ...GE NUTRI USER S GUIDE GE NUTRI Section C 21 USER S GUIDE GE NUTRI SECTION C...
Page 71: ...GE NUTRI INDEX WARRANTY GE NUTRI Section D 71 INDEX WARRANTY GE NUTRI SECTION D...
Page 75: ......