GE-NUTRI USER’S GUIDE
GE-NUTRI
Section C-49
MAIN
MENU
SETTINGS PROGRAM {1-4}
MIN TIME ALARMS PROG {1-4}
1.
These parameters are used to choose if the maximum alarm time is active
for the feeder or for feed augers assigned to the corresponding feed. If this
parameter is set to
"ON"
, the minimum alarm time goes on when the feed
auger assigned to the corresponding feed receives an activation request, but
won’t be activated for longer than
TEMPS MIN[2].
2.
These parameters are used to set the time limit for each minimum time feed
auger alarm assigned to the corresponding feed. When a feed auger does
not operate and it has a request for a period exceeding its assigned feed
limit, the alarm activates. Besides, if applicable, the backup of the
corresponding feed will be used instead of the depleted one. In multi-feed
mode, if the active feed has no reserve, the program goes to the feeder
phase. In chain feeder and drop chain feeder mode, the cycle is canceled. In
feed auger and drop feed auger mode, the feed augers assigned to the
corresponding feed stop operating. When this limits it exceed, the
corresponding bin is considered empty. This parameter can be set from 0:00
to 300:59 minutes.
M i n T i m e A l a r m s P #
O p t i o n T i m e
F e e d e r : O F F 5 : 0 0
F e e d 1 : O N 5 : 0 0
F e e d 2 : O F F 5 : 0 0
F e e d 3 : O F F 5 : 0 0
F e e d 4 : O F F 5 : 0 0
[1]
[2]
Summary of Contents for GE-NUTRI
Page 3: ...GE NUTRI WIRING DIAGRAM GE NUTRI Section A 3 WIRING DIAGRAM GE NUTRI SECTION A...
Page 10: ...GE NUTRI INSTALLATION Section B 10 GE NUTRI INSTALLATION GE NUTRI SECTION B...
Page 21: ...GE NUTRI USER S GUIDE GE NUTRI Section C 21 USER S GUIDE GE NUTRI SECTION C...
Page 71: ...GE NUTRI INDEX WARRANTY GE NUTRI Section D 71 INDEX WARRANTY GE NUTRI SECTION D...
Page 75: ......