GE-NUTRI INSTALLATION
GE-NUTRI
Section B-19
OUTPUT RELAYS (2HP)
Maximum Load
2HP @ 240VAC, 1HP @ 120VAC, 12A@240VAC
Notice
These relays are rated by UL and CSA at 2HP @
240VAC, 1HP @ 120VAC. However, for outputs
requiring frequent activation (ex: minimum
ventilation fans working on a timer) it is
recommended not to use more than 1HP @
240VAC, 1/2HP @ 120VAC per relay.
VARIABLE OUTPUTS
Maximum Allowable Current (Fuse value)
15A, 250VAC
Recommended maximum current for fans
12A, 120 / 208 / 240VAC
Minimum load
300mA @ 230VAC
PLS OUTPUTS
Recommended wires
2 conductors, twisted pair (8 twist /ft), AWG #22
Maximum wire length (350pF/m cable)
160ft (50m)
Maximum wire length (89pF/m cable)
650ft (200m)
Important Notice:
-
It is important to have a backup system in case of a system failure.
-
Low-voltage and high-voltage wires must be passed through different
conduits at least 1 foot (30 cm) apart. If low-voltage and high-voltage
conduits must be crossed, the crossing must be at a 90-degree angle.
-
All wiring must be made by a certified electrician and conform to local
electrical regulations.