10-20 VersaMax Modules, Power Supplies and Carriers User's Manual
GFK-1504N
10
IC200ALG260
Analog Input Module, 12 Bit Voltage/Current 8 Channels
Jumper Selections
Jumpers on JMP 1 and JMP 2 select voltage or current operation and voltage
range. In current mode, JMP2 is ignored.
Jumper
Range
None
±10V
1
4-20mA
2
0-10V
1 & 2
Not recommended
Wiring Examples
Voltage Inputs
Current Inputs
Voltage
Source
Voltage
Source
Current
Source
Current
Source
I 1
V 1
V 8
I 1
Return (common)
V 1
V 8
JMP 2B
JMP 2B
JMP 1B
JMP 1B
Jumper present
selects 0-10V
Inputs
I 8
JMP 1A
JMP 2A
I 8
JMP 1A
JMP 2A
Jumper present
selects Current
Inputs
Return (common)
Return (common)
Return (common)
An external source must be provided to power input transceivers.