9-36 VersaMax Modules, Power Supplies and Carriers User's Manual
GFK-1504N
9
IC200MDD847
Mixed Module, Output Relay 2.0 A per Pt Isolated 8 Points /
Input 240 V AC Grouped 8 Points
Field Wiring
Terminal
Connection
Terminal
Connection
A1
Output 1-1
B1
Input 1
A2
Output 1-2
B2
Input 2
A3
Output 2-1
B3
Input 3
A4
Output 2-2
B4
Input 4
A5
Output 3-1
B5
Input 5
A6
Output 3-2
B6
Input 6
A7
Output 4-1
B7
Input 7
A8
Output 4-2
B8
Input 8
A9
Output 5-1
B9
No connection
A10
Output 5-2
B10
No connection
A11
Output 6-1
B11
No connection
A12
Output 6-2
B12
No connection
A13
Output 7-1
B13
No connection
A14
Output 7-2
B14
No connection
A15
Output 8-1
B15
No connection
A16
Output 8-2
B16
No connection
A17
No connection
B17
Inputs 1-8 Common (Return)
A18
No connection
B18
No connection
Outputs are individually isolated. When wiring outputs to inductive loads, use of
external suppression circuits is recommended. Refer to chapter 2, Installing
Wiring for I/O Devices-Wiring to Inductive Loads.
Wiring Connections
for Carriers with Two
Rows of Terminals
IC200CHS002, 005
IC200CHS012, 015
Q1
Q2
Q3
Q4
Q5
Q6
Q7
Q8
v
v
v
v
v
v
v
v
I1
I2
I3
I4
I5
I6
I7
I8
N
H
1
2
3
4
5
6
7
8
9
11
12
13
14
15
16
17
18
1
2
3
4
5
6
7
8
9
11
12
13
14
15
16
17
18
10
10
B
A
Wiring Connections
for Carriers with
Three Rows of
Terminals
IC200CHS001, 022, 025
IC200CHS011
1
2
3
4
5
6
1
2
3
4
5
6
13
14
15
16
17
18
7
8
9
11
12
10
A
13
14
15
16
17
18
7
8
9
11
12
10
I1
I2
I3
I4
I5
I6
I7
I8
B
Q4
Q5
Q6
Q7
Q8
v
v
v
v
v
Q1
Q2
Q3
v
v
v
N
H