1
Expansion Modules
There are two basic types of VersaMax I/O expansion systems, Multi-Rack and
Two-Rack Local:
Multi-Rack:
A VersaMax PLC or NIU I/O Station with an Expansion
Transmitter Module (IC200ETM001) and one to seven expansion “racks”,
each with an Expansion Receiver Module (IC200ERM001 or
IC200ERM002). If all the Expansion Receivers are the Isolated type
(IC200ERM001), the maximum overall cable length is 750 meters. If the
expansion bus includes any non-isolated Expansion Receivers
(IC200ERM002), the maximum overall cable length is 15 meters.
PS
CPU/NIU
PS
ERM
PS
ERM
ETM
VersaMax ExpansionRack 1
Terminator
Plug
15M with any
IC200ERM 002 ERM s
750M with all
IC200ERM 001 ERM s
VersaMax PLC or I/O Station M ain Rack (0)
VersaMax ExpansionRack 7
IC200CBL601,
602, 615
Two-Rack Local:
A CPU or NIU I/O Station connected directly to one
expansion rack with non-isolated Expansion Receiver Module
(IC200ERM002). Maximum cable length is 1 meter.
PS
ERM
VersaMax Expansion Rack
1 M
VersaMax PLC or NIU I/O Station Main Rack
PS
CPU/NIU
IC200CBL601