4-10 VersaMax Modules, Power Supplies and Carriers User's Manual
GFK-1504N
4
IC200CHS003
Connector-Style I/O Carrier
Field Wiring Connection
I/O devices can be wired directly to Interposing I/O Terminals, described
separately in this chapter, or other types of terminal strips.
Connection to the Connector Style I/O Carrier is made by cable. The following
cables are available:
IC200CBL105 2 connectors, 0.5m, no shield
IC200CBL110 2 connectors, 1.0m, no shield
IC200CBL120 2 connectors, 2.0m, no shield
IC200CBL230 1 connector, 3.0m, no shield
The notch on the connector indicates the orientation of the pins.
A1
A2
A3
A4
A5
B5
B6
B3
B4
B1
B2
A6
A7
A8
A9
A10
B12 B9
B10
B7
B8
A11 A12 A13
A14 A15 A16
B15
B16 B13
B14 B11
B17
B18
A17
A18
A connector kit is available for building custom cables. The kit is part number
IC200ACC304.
The carrier accommodates current levels up to 2 A per point or 8 A per each
power and ground, and a voltage range of up to 264 V AC. Voltage transients
up to 300 V AC will not damage the carrier.
Compatibility
This carrier can be used with all VersaMax I/O modules EXCEPT the following,
due to their high isolation requirements:
IC200MDL144 Input 240 V AC 4 Point Isolated Module
IC200MDL244 Input 240 V AC 8 Point Isolated Module
IC200MDD850 Mixed 240 V AC Isolated 4 Point / Output Relay 2.0 A
Isolated 8 Point Module