6-18
VersaMax Modules, Power Supplies and Carriers
GFK-1504N
6
IC200ERM002
Expansion Receiver Module, Non-isolated
Module Specifications
Module Characteristics
LED indicators
PWR LED indicates 5 V DC power status
EXP RX LED indicates expansion bus communications status
SCAN LED indicates whether the CPU/NIU is scanning I/O in
expansion racks
Backplane current
consumption
5V output: 70mA maximum
3.3V output: 20mA
Compatibility
Cimplicity
ME
Versa
Pro
Control
90
CPU
001
CPU
002
CPU
005
CPU
E05
DBI
001
EBI
001
GBI
001
PBI
001
HW,FW rel.
FW version #
2.11
1.1
No
BD
1.5
AA
1.5
AA
2.1
AA
2.1
No
AB
1.1
AC
1.5
BD
2.01
Cable Specifications
Maximum cable length
Effective data rate
Electrical Isolation
15 meters (differential) , 1 m (single-ended)
5 Mbits/sec (differential), 2.765 Mbits/sec (single-ended)
Non-isolated differential or single-ended communications
Catalog Numbers
Bus Receiver Module
IC200ERM002
Expansion Cable,
Shielded
Terminator Plug
Connector Kit
IC200CBL601 - 1 m
IC200CBL602 - 2 m
IC200CBL615 - 15 m
IC200ACC201 (included with ETM)
IC200ACC202
Modules for Expansion Racks
All I/O and communications modules can be used in expansion racks. Some
analog modules require specific module revisions as listed below. The date
code is a 3-digit number on the outside of the module and on the shipping box.
Module
Revision
Module Date Code Range
IC200ALG320
B or later
Any
IC200ALG321
B or later
Any
IC200ALG322
B or later
Any
IC200ALG430
C or later
Any
IC200ALG431
C or later
Any
IC200ALG432
B or later
Any
IC200ALG230
A or later
CPU or NIU Revision 1.5:
Date code must begin with a
number other than 9 and must be 011 or greater.
Any
CPU or NIU Revision 2.0 or later:
Any date code.
IC200ALG260
A or later
CPU or NIU Revision 1.5:
Date code must begin with a
number other than 9 and must be 011 or greater.
Any
CPU or NIU Revision 2.0 or later:
Any date code.