9-18 VersaMax Modules, Power Supplies and Carriers User's Manual
GFK-1504N
9
Configuration Parameters
The module’s basic input on/off response time is 0.5ms. For some applications, it
may be preferable to add additional filtering to compensate for conditions such as
noise spikes or switch bounce. Input filter times of 0ms, 1.0ms, or 7.0ms are
selectable through software configuration, for total response times of 0.5ms,
1.5ms, and 7.5ms respectively. The default is 1.0ms filter time (total response
time is 1.5ms).