GFK-1504N
Chapter 11 Analog Output Modules
11-37
11
IC200ALG327
Analog Output Module, 13 Bit Voltage 12 Channels
Jumper Selection
Jumpers on the carrier can be used to select the output range and output
default mode.
Range Jumper
If no jumper is installed on pins B1 and B2, outputs are configured for the
bipolar range of –10V to +10V. With a jumper installed, the outputs are
configured for the unipolar range of 0V to +10V.
Range Jumper (JMP 1)
Range
None
-10V to +10V
Installed
0V to +10V
Hold Jumper
If no jumper is installed on pins B2 and B3, outputs hold their last state (the last
commanded value from the backplane) if backplane power or communications
are interrupted or the PLC is stopped. With a jumper installed, outputs default
to 0V. This should only be changed with the field power and backplane power
removed.
Hold Jumper (JMP 2)
Output Default
None
Hold Last State
Installed
0V
Wiring Example
JMP 2
Jumper installed = unipolar range
no jumper = bipolar range
JMP 1
Field Power
Field Return
-
+
Load 1
Shield
V OUT 1
Return 1, 2
Load 2
V OUT 2
Shield
RET
Jumper installed = default to 0V
no jumper = hold last state