GFK-1504N
Chapter 8 Discrete Output Modules
8-49
8
IC200MDL940
Output Module, Relay 2.0 A, Isolated Form A 16 Points
Backplane Power Drain per Point
The module’s backplane 5 volt power requirement increases as the number of
points that are simultaneously on increases. The following chart displays the
relationship between the number of points on and the maximum current
required.
mA = 13 + (28 x number of points on)
Number of Points On
Maximum Current Drawn from Backplane (mA)
0
4
8
245
128
13