GFK-1504N
Chapter 11 Analog Output Modules
11-5
11
IC200ALG320
Analog Output Module, 12 Bit Current, 4 Channels
Jumper Selection
If no jumper is installed outputs hold their last state (the last commanded value
from the backplane) if backplane power or communications are interrupted or
the PLC is stopped. With a jumper installed, if such conditions occur outputs
default to 4mA. This should only be changed with field power and backplane
power removed.
Jumper
Default
None
Hold Last State
JMP 1
4mA
Wiring Example
IOUT 4
RET 4
JMP 1A
JMP 1B
Field Power
Field Return
IOUT 1
RET 1
-
+
Shield
Shield
24VDC
Load
Load
Jumper installed =default to 4mA
no jumper = hold last state