9-16 VersaMax Modules, Power Supplies and Carriers User's Manual
GFK-1504N
9
IC200MDD843
Mixed Module, 24 V DC Positive Logic Input Grouped 10 Points /
Output Relay 2.0 A per Point Grouped 6 Points
Backplane Power Drain per Point
The module’s backplane 5 V power requirement increases as the number of
points that are simultaneously on increases. The following chart displays the
relationship between the number of points on and the maximum current required.
mA = 40 + (28 x number of output points on)
Number of Output Points On
Maximum Current Drawn from Backplane (mA)
0
3
6
190
104
20