GFK-1504N
Chapter 2 Installation
2-25
2
Installing and Removing a Prewired Cable
To install a prewired connecting cable, place the cable connector over the
connector on the carrier and press downward until the latch engages the tab on
the connector.
Latch
Cable
To remove the cable, hold the cable connector and press up on the latch to
release the connector. When removing the cable, remember that operating
equipment may be very hot, especially at higher ambient temperatures. If the
equipment is hot, do not touch it directly.
DO NOT TOUCH exposed connector pins if the system is operating.
Connector Kit
A connector kit (part number IC200ACC304) is available for building custom
cables or for connecting wires directly from field devices. The kit includes two
connectors and covers, four screws, 27 small contacts, and 12 large contacts.
The following equipment is also required but not included in the kit:
Crimping Tools
small contact
Molex 11-01-0008
large contact
Molex 11-01-0084
Extraction Tools
small contact
Molex 11-03-0002
large contact
Molex 11-03-0006
Terminal Numbering
The following illustration displays the terminal assignments of the connector
pins as viewed from above.
A1
A2
A3
A4
A5
B5
B6
B3
B4
B1
B2
A6
A7
A8
A9
A10
B12 B9
B10
B7
B8
A11 A12 A13
A14 A15 A16
B15
B16 B13 B14 B11
B17
B18
A17
A18
B terminals
A terminals
Cable