GFK-1504N
Chapter 12 Analog Mixed I/O Modules
12-5
12
IC200ALG430
Analog Mixed Module, 12 Bit Input Current 4 Channels and
Output Current 2 Channels
Jumper Selection
A jumper on the carrier can be used to select the output default mode. If no
jumper is installed on pins B13 and B14 outputs hold their last state (the last
commanded value from the backplane) if backplane power or communications
are interrupted or the PLC is stopped. With a jumper installed, if such
conditions occur outputs default to 4mA. This should only be changed with field
power and backplane power removed.
Jumper
Selects
None
Hold Last State
JMP 1
Default to 4mA
Wiring Examples
Current Inputs
Current
Source
Current
Source
I In 1 +
I In 1 -
JMP 1A
JMP 1B
Field Power
Field Return
I Out 1
RET 1
-
+
Shield
24VDC
Load
I Out 2
RET 2
Shield
Load
Jumper installed =default to 4mA
no jumper = hold last state
Current Outputs
I In 4 +
I In 4 -
An external source is needed to
power input transceivers.