11-54 VersaMax Modules, Power Supplies and Carriers User's Manual
GFK-1504N
11
IC200ALG331
Analog Output Module, 16 Bit Voltage/Current, 1500 V AC Isolation, 4
Channels
Configurable Parameters
The default parameters of this module can be used in many applications. The
module can be software-configured when it is installed in a VersaMax PLC
system, or an I/O Station controlled by a NIU that is version 2.0 or above.
Module
Parameter
Description
Default
Choices
Analog Output
Data
Reference
Starting offset for the module’s analog output data.
user selectable
Analog Output
Data Length
Word length of the module’s analog output data.
4
0–4
Report Faults Enables or disables Fault Reporting for the entire
Module.
Enabled
Enabled,
Disabled
%AQ Default
/Hold Last
State
Specifies whether the module will go to the
specified channel defaults (see below) or hold
their last states if power or communications are
lost.
Default
Default /Hold
Current /
Voltage
Specifies whether the channel will be a voltage or
current output.
If the Channel type is Current, the range is 4 to
20mA.
If Channel type is Voltage, the range is –10 to
+10V.
I (Current)
I (Current),
V (Voltage)
Channel
Active
Specifies if the channel should output data
received from the CPU or NIU. If a channel is
“inactive” space is still allocated for it.
Active
Inactive (off), Active (on)
Span Low
Actual current (in microAmps) or voltage (in
milliVolts) to be scaled to low engineering units
value.
4000
µ
A
0 to 25,000
µ
A
–10,000 to +10,000mV
Span High
Actual current in microAmps or voltage in millivolts
to be scaled to the high engineering units value.
20000
µ
A
0 to 25,000
µ
A
–10,000 to +10,000mV
Engineering
Low
The engineering units value that is considered
equivalent to the low span (actual) value.
4000
0 to 25,000
µ
A
–10,000 to +10,000mV
Engineering
High
The engineering units value that is considered
equivalent to the high span (actual) value.
20000
0 to 25,000
µ
A
–10,000 to +10,000mV
Default
The value to be output by the firmware when the
module is in a default condition and the Output
Default Control is set to Default.
0
µ
A
-32768 to +32767