7-
10
SPM Synchronous Motor Protection & Control
GE Power Management
7.5 PROGRAMMING
7 TESTING AND TROUBLESHOOTING
7
,
Change the existing value of SYNC SLIP to 4.0%. SCROLL
Key(s) to select value of 4% and then SELECT/ENTER key to
accept new value
,
SCROLL DOWN key to move to the STALL TIME setpoint then
SELECT/ENTER to select the setpoint
,
Change the existing value of STALL TIME to 7 seconds. SCROLL
Key(s) to select value of 7s and then SELECT/ENTER key to
accept new value
,
SCROLL DOWN key to move to the RUNTIME setpoint then
SELECT/ENTER to select the setpoint
,
Change the existing value of RUNTIME to 1.46 times the stall
time. SCROLL Key(s) to select value of 1.46 and then SELECT/
ENTER key to accept new value
,
SCROLL DOWN key to move to the DC CT PRIM setpoint then
SELECT/ENTER to select the setpoint
,
Change the existing value of DC CT PRIM to 100A. SCROLL
Key(s) to select value of 100 and then SELECT/ENTER key to
accept new value.
SCROLL DOWN key to move to the HIGH FIELD setpoint. This
value will remain as is.
,
SCROLL DOWN key to move to the FIELD AMPS setpoint then
SELECT/ENTER to select the setpoint.
,
Change the existing value of FIELD AMPS to 45. SCROLL Key(s)
to select value of 45 and then SELECT/ENTER key to accept new
value
,
SCROLL DOWN key to move to the FIELD VOLTS setpoint then
SELECT/ENTER to select the setpoint
,
Change the existing value of FIELD VOLTS to 125. SCROLL
Key(s) to select value of 125 and then SELECT/ENTER key to
accept new value.
,
SCROLL DOWN key to move to INC SEQ DLY setpoint then
SELECT/ENTER to select the setpoint
,
Change the existing value of INC SEQ DLY to 15 seconds.
SCROLL Key(s) to select value of 15 and then SELECT/ENTER
key to accept new value.
Table 7–2: PROGRAMMING EXAMPLE (Sheet 3 of 4)
KEYPRESS
DISPLAY
COMMENTS
ENTER
SYNC SLIP:
4.0%
SCROLL to change
ENTER
STALL TIME:
40 s
ENTER to modify
ENTER
STALL TIME:
7 s
SCROLL to change
ENTER
RUNTIME: 3.00 x ST
ENTER to modify
ENTER
RUNTIME: 1.46 x ST
SCROLL to change
ENTER
DC CT PRIM:
20 A
ENTER to modify
ENTER
DC CT PRIM:
100 A
SCROLL to change
HIGH FIELD:
10.0
Ω
ENTER to modify
ENTER
FIELD AMPS: OFF
ENTER to modify
ENTER
FIELD AMPS:
45
SCROLL to change
ENTER
FIELD VOLTS:
25
ENTER to modify
ENTER
FIELD VOLTS: 125
SCROLL to change
ENTER
INC SEQ DLY: 100 s
ENTER to modify
ENTER
INC SEQ DLY: 15 s
SCROLL to change
Summary of Contents for SPM Series
Page 2: ......
Page 4: ......
Page 10: ...vi SPM Synchronous Motor Protection Control GE Power Management TABLE OF CONTENTS...
Page 74: ...6 4 SPM Synchronous Motor Protection Control GE Power Management 6 2 STATUS 6 ACTUAL VALUES 6...
Page 120: ...C 2 SPM Synchronous Motor Protection Control GE Power Management C 1 WARRANTY APPENDIXC C...
Page 124: ...iv SPM Synchronous Motor Protection Control GE Power Management INDEX...
Page 125: ...GE Power Management SPM Synchronous Motor Protection Control NOTES...