GE Power Management
SPM Synchronous Motor Protection & Control
5-
9
5 SETPOINTS
5.2 SETPOINTS MENU
5
5.2.18 FIELD UNDERVOLTAGE DELAY
FUNCTION:
The exciter voltage delay setpoint is the time delay that will elapse after the exciter voltage falls below the pro-
grammed setpoint before the SPM initiates tripping action for field undervoltage (
CHECK EXCITER
)
MOTOR TYPE:
Collector-Ring or Brushless
NOTE:
The
EXCITER VOLTS
option must be enable before this feature can be used.
5.2.19 INCOMPLETE SEQUENCE DELAY
FUNCTION:
If the SPM does not properly complete its starting sequence in the setpoint time, the SPM will trip and display
an in-complete sequence condition.
COLLECTOR-RING: The time setting may be set to a value between 1 and 100 seconds, but not less than the
FCX delay setpoint.
BRUSHLESS: The time setting may be set to a value between 1 and 200 seconds, but not less than the sum of
the FAR delay setpoint and the FCX delay setpoint.
MOTOR TYPE:
Collector-Ring or Brushless
FLD VLT DLY: N/A
ENTER to modify
Range: N/A, 0.3 to 5 seconds
Step: 0.1 for values
<
1 second; 1 for values
≥
1 second
INC SEQ DLY:
OFF
ENTER to modify
Collector-Ring
Range: 1 to 100 seconds, OFF
Step 1
INC SEQ DLY:
OFF
ENTER to modify
Brushless
Range: 1 to 200 seconds, OFF
Step 1
Summary of Contents for SPM Series
Page 2: ......
Page 4: ......
Page 10: ...vi SPM Synchronous Motor Protection Control GE Power Management TABLE OF CONTENTS...
Page 74: ...6 4 SPM Synchronous Motor Protection Control GE Power Management 6 2 STATUS 6 ACTUAL VALUES 6...
Page 120: ...C 2 SPM Synchronous Motor Protection Control GE Power Management C 1 WARRANTY APPENDIXC C...
Page 124: ...iv SPM Synchronous Motor Protection Control GE Power Management INDEX...