GE Power Management
SPM Synchronous Motor Protection & Control
9-
5
9 MODBUS COMMUNICATIONS
9.2 MEMORY MAPPING
9
SYSTEM
CALIBRATION
1050
FULL SCALE EXCITER DC VOLTAGE
0.6 to 1.5
0.01
-
U16
100
1051
FULL SCALE EXCITER DC AMPS
0.6 to 1.5
0.01
-
U16
100
1052
FULL SCALE MOTOR AC AMPS
0.6 to 1.5
0.01
-
U16
100
1053
Reserved
↓
↓
↓
↓
↓
↓
↓
10FF
Reserved
POWER
FACTOR
1100
PF TRIP
–0.60 to 1.00
0.01
-
2decS16
60
1101
PF DELAY
0.1 to 10.0
0.1
s
1decU16
50
1102
PF SUPPRESSION
6 or 50
-
%FLC
U16
6
1103
PF MODE
0 or 1
PFmode
0
1104
Reserved
↓
↓
↓
↓
↓
↓
↓
110F
Reserved
FIELD/LOAD
APPLICATION
1110
FAR DELAY
0 to 90
1
s
U16
0
1111
FCX DELAY
1 to 6 *
1 to 90 **
1
s
U16
1
1112
Reserved
↓
↓
↓
↓
↓
↓
↓
111F
Reserved
MOTOR /
AC SYSTEM
1120
AC CT RATIO
5 to 2000
5
:5
U16
50
1121
FULL LOAD AMPS
2 to 2000
2
1
A
U16
25
1122
LOCKED ROTOR AMPS
4 to 24000
3
1
A
U16
200
1123
Reserved
↓
↓
↓
↓
↓
↓
↓
112F
Reserved
STARTING
SETPOINTS
1130
SYNCHRONOUS SLIP
0.5 to 10.0
0.1
%
1decU16
50
1131
STALL TIME
1 to 40
1
s
U16
10
1132
RUN TIME
1.05, 1.46,
2.05, 3.00
-
×
stall time
Runtime
3
1133
INCOMPLETE SEQUENCE DELAY
(max+1 = OFF)
1 to 100 or OFF *
1 to 200 or OFF **
1
s
U16
201
1134
Reserved
↓
↓
↓
↓
↓
↓
↓
113F
Reserved
Table 9–2: MODBUS MEMORY MAP (Sheet 4 of 5)
GROUP
ADDR
(hex)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
*
Range for collector-ring motors.
** Range for brushless motors.
1. The access password must be written correctly before any setpoints can be written via Modbus. The password is initially the same as the default password,
but the two passwords are stored separately, so the keyboard can not be used to change the communications password and vice-versa.
2. The allowable range of FLA is as follows: the minimum full load amps value is 2/5 times the CT ratio; the maximum is equal to the CT ratio.
3. The locked rotor current is range dependent on the FLA setpoint: the minimum is twice the full load amps and the maximum value is 12 times the FLA.
4. REGULATOR OUTPUT must be greater than or equal to FLOOR VOLTS, likewise FLOOR VOLTS must be less than or equal to REGULATOR OUTPUT.
Summary of Contents for SPM Series
Page 2: ......
Page 4: ......
Page 10: ...vi SPM Synchronous Motor Protection Control GE Power Management TABLE OF CONTENTS...
Page 74: ...6 4 SPM Synchronous Motor Protection Control GE Power Management 6 2 STATUS 6 ACTUAL VALUES 6...
Page 120: ...C 2 SPM Synchronous Motor Protection Control GE Power Management C 1 WARRANTY APPENDIXC C...
Page 124: ...iv SPM Synchronous Motor Protection Control GE Power Management INDEX...
Page 125: ...GE Power Management SPM Synchronous Motor Protection Control NOTES...