GE Power Management
SPM Synchronous Motor Protection & Control
7-
9
7 TESTING AND TROUBLESHOOTING
7.5 PROGRAMMING
7
,
Change existing value of PF TRIP to new –0.85 value.
,
Select the setpoint. Use the scroll key(s) to select value of 5.0
seconds and then ENTER to accept new value
,
Change the existing value of PF DELAY to 5.0
This value will remain as is.
,
Select the setpoint. Use the scroll keys to move to the PF MODE
setpoint and then ENTER to select the setpoint.
,
Change the existing value of PF MODE to resync. Use the scroll
keys to select value of resync and then ENTER to accept new
value.
Press the scroll down key to move to the FCX delay setpoint. This
value will remain as is.
,
SCROLL DOWN key to move to the AC CT RTG setpoint and then
SELECT/ENTER key to select the setpoint.
,
Change the existing value of AC CT RTG to 100. SCROLL Key(s)
to select the value of 100 then SELECT/ENTER key to accept new
value.
,
SCROLL DOWN key to move to the FL AMPS setpoint and then
SELECT/ENTER key to select the setpoint
,
Changes existing value of FL AMPS to 56. SCROLL Key(s) to
select value of 58 and then SELECT/ENTER key to accept new
value
,
SCROLL DOWN key to move to the LR AMPS setpoint and then
SELECT/ENTER to select the setpoint
,
Change the existing value of LR AMPS to 226. SCROLL Key(s) to
select value of 226 and then SELECT/ENTER key to accept new
value
,
SCROLL DOWN key to the SYNC SLIP set-point and then
SELECT/ENTER key to select the setpoint
Table 7–2: PROGRAMMING EXAMPLE (Sheet 2 of 4)
KEYPRESS
DISPLAY
COMMENTS
ENTER
PF TRIP:
–0.85
ENTER to modify
ENTER
PF DELAY: 10.0 s
ENTER to modify
ENTER
PF DELAY: 5.0 s
ENTER to modify
PF SUPP: 6% FLC
ENTER to modify
ENTER
PF MODE: ridethru
ENTER to modify
ENTER
PF MODE: resync
SCROLL to change
FCX DELAY: 1 s
ENTER to modify
ENTER
AC CT RTG: 10/5
ENTER to modify
ENTER
AC CT RTG: 100/5
SCROLL to change
ENTER
FL AMPS:
10
ENTER to modify
ENTER
FL AMPS:
58
SCROLL to change
ENTER
LR AMPS:
116
ENTER to modify
ENTER
LR AMPS:
226
SCROLL to change
ENTER
SYNC SLIP:
0.5%
ENTER to modify
Summary of Contents for SPM Series
Page 2: ......
Page 4: ......
Page 10: ...vi SPM Synchronous Motor Protection Control GE Power Management TABLE OF CONTENTS...
Page 74: ...6 4 SPM Synchronous Motor Protection Control GE Power Management 6 2 STATUS 6 ACTUAL VALUES 6...
Page 120: ...C 2 SPM Synchronous Motor Protection Control GE Power Management C 1 WARRANTY APPENDIXC C...
Page 124: ...iv SPM Synchronous Motor Protection Control GE Power Management INDEX...
Page 125: ...GE Power Management SPM Synchronous Motor Protection Control NOTES...