SPM Synchronous Motor Protection & Control
GE Power Management
9.2 MEMORY MAPPING
9 MODBUS COMMUNICATIONS
9
9.2 MEMORY MAPPING
9.2.1 MODBUS MEMORY MAP
Table 9–2: MODBUS MEMORY MAP (Sheet 1 of 5)
GROUP
ADDR
(hex)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
Product ID (Input registers at addresses 0000 to 007F)
PRODUCT
ID
0000
GE Product Device Code
N/A
N/A
N/A
U16
40
0001
Product Hardware Revision
1 to 26
1
N/A
Alpha
N/A
0002
Product Software Revision
N/A
N/A
N/A
Revcode
N/A
0003
Product Modification Number
0 to 999
1
N/A
U16
N/A
0004
Reserved
↓
↓
↓
↓
↓
↓
↓
007F
Reserved
Actual Values (Input registers at addresses 0200 to 0FFF)
MOTOR
STATUS
0200
Motor Status
Motorstatus
N/A
0201
Estimated Time to Trip for Stall
U16
N/A
0202
Reserved
↓
↓
↓
↓
↓
↓
↓
020F
Reserved
TRIP
DATA
0210
Cause of Trip
Tripcause
N/A
0211
Lockout Time
U16
N/A
0212
Reserved
↓
↓
↓
↓
↓
↓
↓
021F
Reserved
LINE
CURRENT
0220
Instantaneous Line Current
U16
N/A
0221
Filtered Line Current
U16
N/A
0222
Reserved
0223
Reserved
0224
Reserved
LINE
VOLTAGE
0225
Instantaneous Motor Voltage
U16
N/A
0226
Filtered Motor Voltage
U16
N/A
0227
Reserved
0228
Reserved
0229
Reserved
*
Range for collector-ring motors.
** Range for brushless motors.
1. The access password must be written correctly before any setpoints can be written via Modbus. The password is initially the same as the default password,
but the two passwords are stored separately, so the keyboard can not be used to change the communications password and vice-versa.
2. The allowable range of FLA is as follows: the minimum full load amps value is 2/5 times the CT ratio; the maximum is equal to the CT ratio.
3. The locked rotor current is range dependent on the FLA setpoint: the minimum is twice the full load amps and the maximum value is 12 times the FLA.
4. REGULATOR OUTPUT must be greater than or equal to FLOOR VOLTS, likewise FLOOR VOLTS must be less than or equal to REGULATOR OUTPUT.
Summary of Contents for SPM Series
Page 2: ......
Page 4: ......
Page 10: ...vi SPM Synchronous Motor Protection Control GE Power Management TABLE OF CONTENTS...
Page 74: ...6 4 SPM Synchronous Motor Protection Control GE Power Management 6 2 STATUS 6 ACTUAL VALUES 6...
Page 120: ...C 2 SPM Synchronous Motor Protection Control GE Power Management C 1 WARRANTY APPENDIXC C...
Page 124: ...iv SPM Synchronous Motor Protection Control GE Power Management INDEX...
Page 125: ...GE Power Management SPM Synchronous Motor Protection Control NOTES...