SPM Synchronous Motor Protection & Control
GE Power Management
9.2 MEMORY MAPPING
9 MODBUS COMMUNICATIONS
9
DC SYSTEM
1140
DC CT PRIMARY
5 to 1000
1
A
U16
5
1141
HIGH (EXCITER) FIELD
(max+1 = OFF)
0.20 to 450.00
or OFF
0.01,
0.10, 1.00
Ω
2decU16
0
1142
(EXCITER) FIELD AMPS
(zero = OFF)
0.1 to 1000.0
or OFF
0.1 if <10A
1.0 if
≥
10A
A
1decU16
0
1143
(EXCITER) FIELD VOLTS (zero = OFF)
1 to 200 or OFF
1
V
U16
0
1144
(EXCITER) FIELD AMPS DELAY
0.3 to 5.0
0.1
s
1decS16
0.3
1145
(EXCITER) FIELD VOLTS DELAY
0.3 to 5.0
0.1
s
1decS16
0.3
1146
Reserved
↓
↓
↓
↓
↓
↓
↓
114F
Reserved
PF
REGULATION
1150
PF REGULATION LEVEL (max+1 = OFF) –0.90 to 1.00 / OFF
0.01
-
2decS16
111
1151
REGULATOR GAIN
1 to 100
1
-
U16
1
1152
STABILITY
1 to 60
1
-
U16
1
1153
REGULATOR OUTPUT
0 to 10
4
1
V
U16
1
1154
FLOOR VOLTS
0.0 to 10.0
4
0.1
V
1decU16
0
1155
Reserved
↓
↓
↓
↓
↓
↓
↓
115F
Reserved
Table 9–2: MODBUS MEMORY MAP (Sheet 5 of 5)
GROUP
ADDR
(hex)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
*
Range for collector-ring motors.
** Range for brushless motors.
1. The access password must be written correctly before any setpoints can be written via Modbus. The password is initially the same as the default password,
but the two passwords are stored separately, so the keyboard can not be used to change the communications password and vice-versa.
2. The allowable range of FLA is as follows: the minimum full load amps value is 2/5 times the CT ratio; the maximum is equal to the CT ratio.
3. The locked rotor current is range dependent on the FLA setpoint: the minimum is twice the full load amps and the maximum value is 12 times the FLA.
4. REGULATOR OUTPUT must be greater than or equal to FLOOR VOLTS, likewise FLOOR VOLTS must be less than or equal to REGULATOR OUTPUT.
Summary of Contents for SPM Series
Page 2: ......
Page 4: ......
Page 10: ...vi SPM Synchronous Motor Protection Control GE Power Management TABLE OF CONTENTS...
Page 74: ...6 4 SPM Synchronous Motor Protection Control GE Power Management 6 2 STATUS 6 ACTUAL VALUES 6...
Page 120: ...C 2 SPM Synchronous Motor Protection Control GE Power Management C 1 WARRANTY APPENDIXC C...
Page 124: ...iv SPM Synchronous Motor Protection Control GE Power Management INDEX...
Page 125: ...GE Power Management SPM Synchronous Motor Protection Control NOTES...