SPM Synchronous Motor Protection & Control
GE Power Management
9.2 MEMORY MAPPING
9 MODBUS COMMUNICATIONS
9
DIGITAL
INPUTS
024C
MX Status
Switchstate
N/A
024D
NX Status
Switchstate
N/A
024E
Reserved
↓
↓
↓
↓
↓
↓
↓
0254
Reserved
STATISTICS
(can be written
as holding
registers)
0255
Motor Running Hours
U16
N/A
0256
Incomplete Sequence Trip Counter
U16
N/A
0257
Field Loss Trip Counter
U16
N/A
0258
Pull Out Trip Counter
U16
N/A
0259
Resynchronization Trip Counter
U16
N/A
025A
Missing External PF Voltage Reference
U16
N/A
025B
Check Exciter Trip Counter
U16
N/A
025C
Power Factor Trip Counter
U16
N/A
025D
Squirrel Cage Trip Counter
U16
N/A
025E
Field Overtemperature Trip Counter
U16
N/A
025F
Reserved
↓
↓
↓
↓
↓
↓
↓
0FFF
Reserved
Setpoints (Holding registers at addresses 1000 to 2FFF)
SYSTEM
CONFIGURATION
1000
ACCESS PASSWORD
1
0 to 9999
1
-
U16
0000
1001
MOTOR TYPE
0 or 1
-
-
Motortype
0
1002
LINE FREQUENCY
0 or 1
-
Hz
Linefreq
0
1003
POWER FACTOR REFERENCE
0 or 1
-
-
PFreg
1
1004
RTU ADDRESS
1 to 254
1
-
U16
1
1005
BAUD RATE
0 to 9
1
baud
Baudrate
6
1006
RS485 PARITY
0 to 2
1
Parity
0
1007
RS485 MIN. TURNAROUND TIME
0
1000
ms
U16
5
1008
STATISTICS MODE
0 or 1
1
-
Startmode
1
1009
NEW PASSWORD
0 to 9999
1
-
U16
4985
1010
Reserved
↓
↓
↓
↓
↓
↓
↓
104F
Reserved
Table 9–2: MODBUS MEMORY MAP (Sheet 3 of 5)
GROUP
ADDR
(hex)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
*
Range for collector-ring motors.
** Range for brushless motors.
1. The access password must be written correctly before any setpoints can be written via Modbus. The password is initially the same as the default password,
but the two passwords are stored separately, so the keyboard can not be used to change the communications password and vice-versa.
2. The allowable range of FLA is as follows: the minimum full load amps value is 2/5 times the CT ratio; the maximum is equal to the CT ratio.
3. The locked rotor current is range dependent on the FLA setpoint: the minimum is twice the full load amps and the maximum value is 12 times the FLA.
4. REGULATOR OUTPUT must be greater than or equal to FLOOR VOLTS, likewise FLOOR VOLTS must be less than or equal to REGULATOR OUTPUT.
Summary of Contents for SPM Series
Page 2: ......
Page 4: ......
Page 10: ...vi SPM Synchronous Motor Protection Control GE Power Management TABLE OF CONTENTS...
Page 74: ...6 4 SPM Synchronous Motor Protection Control GE Power Management 6 2 STATUS 6 ACTUAL VALUES 6...
Page 120: ...C 2 SPM Synchronous Motor Protection Control GE Power Management C 1 WARRANTY APPENDIXC C...
Page 124: ...iv SPM Synchronous Motor Protection Control GE Power Management INDEX...
Page 125: ...GE Power Management SPM Synchronous Motor Protection Control NOTES...