To change SPM setpoints, the user must enter the PROGRAMMING MODE. This can be accomplished with
the motor either off or in running mode. Use the following procedure to enter the PROGRAMMING MODE:
1.
With the display indicating the following, press the GE key (items in bold italics indicate that they should be
blinking on the screen):
2.
The display should now indicate that the unit is in STAT MODE. Press the GE key.
3.
Press the GE key. The display should now indicate that the unit is in PROGRAMMING MODE:
4.
Use the
/
keys to change the password and then press the
key to enter the password.
5.
The display should now indicate the CONFIGURATIONS menu or the CALIBRATION menu (depending
upon which scroll key was pressed). Use the
/
keys to select the SETPOINTS menu.
6.
Press the
key to enter the setpoints menu. Once in the SETPOINTS menu, use the
/
keys to
move through the different setpoints.
7.
To change a setpoint, press the
key as prompted:
8.
Once the setpoint has been selected, the value of the setpoint should blink. Use the
/
keys to
change the value of the setpoint and then press the
key to continue. If you choose not to change this
setpoint once it has been selected, pressing the GE key deselects the setpoint.
9.
Additional setpoints can be changed using the above procedure. When all setpoint changes have been
accomplished, press the GE key. This will return the display to the SETPOINTS main menu. Press the GE
key again and the display will ask to verify that changes should be save. Press
to save the setpoints,
otherwise press the GE key if you do not want to save the changes.
10. Upon pressing
(to save the setpoint changes) or the GE key (not wanting to save setpoint changes),
the display returns to the PROGRAMMING MODE menu. Press the GE key once to go into TEST MODE
and a second time to return to the SPM READY display.
Collr-Ring Motor
SPM READY
STAT MODE
SCROLL for menus
PROGRAMMING MODE
SCROLL PASSWORD
PASSWORD: 0000
ENTER to verify
SETPOINTS?
ENTER for menus
PF TRIP:
–0.80
SELECT to modify
PF TRIP:
–0.80
SCROLL to change
SAVE CHANGES?
ENTER to save ...
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
Summary of Contents for SPM Series
Page 2: ......
Page 4: ......
Page 10: ...vi SPM Synchronous Motor Protection Control GE Power Management TABLE OF CONTENTS...
Page 74: ...6 4 SPM Synchronous Motor Protection Control GE Power Management 6 2 STATUS 6 ACTUAL VALUES 6...
Page 120: ...C 2 SPM Synchronous Motor Protection Control GE Power Management C 1 WARRANTY APPENDIXC C...
Page 124: ...iv SPM Synchronous Motor Protection Control GE Power Management INDEX...
Page 125: ...GE Power Management SPM Synchronous Motor Protection Control NOTES...