1.3 SPECIFICATIONS
1 INTRODUCTION
1
1.3 SPECIFICATIONS
1.3.1 SPM SPECIFICATIONS
PHASE CURRENT INPUTS
CT Primary:
5 to 2000 A
CT Secondary:
5 A
Conversion Range: 0.05 to 6
×
CT
Frequency:
50 / 60 Hz
Accuracy:
at
<
2
×
CT: ±0.5% of 2
×
CT true RMS
at
≥
2
×
CT: ±1% of 6
×
CT true RMS
FIELD CURRENT INPUTS
CT Primary:
5 to 1000 A
Conversion Range: 0.05 to 1
×
CT
Accuracy:
±2%
EXCITER VOLTAGE INPUTS
Conversion:
0 to 350 V DC (prior to VDN)
Accuracy:
±1%
POWER FACTOR
Range:
0.01 to 1 to –0.01
Time Delay:
0.1 to 10 seconds
Accuracy:
±5%
SWITCH INPUTS (MX & NX)
Type:
Dry contact
Internal Interrogation Voltage: 85 to 265 V AC (control voltage)
PF ANALOG OUTPUT
Type:
Active
Output:
0 to 10 V DC max. at
R
L
≥
1 K
Ω
(min. load)
Accuracy:
±10% (0.1 V)
Isolation:
36 V pk
CONTROL VOLTAGE
Input:
85 to 265 V AC at 48 to 60 Hz
Power:
10 VA nominal
Holdup:
100 ms typical at 120 V AC
RELAY CONTACT
Type:
FAR, TRP
Form A
FCX
Form C
Rated Load:
10 A AC continuous
NEMA A300
1 A DC continuous
NEMA R300
Break:
10 A at 250 V AC or 30 V DC
Max. Operating Voltage: 250 V AC
ENVIRONMENT
Humidity:
0 to 95% non-condensing
Operating Temp.:
–20°C to +70°C
Storage Temp.:
–40°C to +85°C
TYPE TESTS
Dielectric Strength: Per IEC 255-5 and ANSI/IEEE C37.90
2.0 kV for 1 min. from relays, CTs, VTs
power supply to Safety Ground
Insulation
Resistance:
IEC255-5 500 VDC, from relays, CTs, VTs
power supply to Safety Ground
Transients:
ANSI C37.90.1 Oscillography (2.5kV/1MHz)
ANSI C37.90.1 Fast Rise (5kV/10ns)
Ontario Hydro A-28M-82
IEC255-4 Impulse/High Frequency Disturbance,
Class III Level
Impulse Test:
IEC 255-5 0.5J 5kV
EMI:
C37.90.2 Electromagnetic Interference at
150 MHz and 450 MHz, 10V/m
Static:
IEC801-2 Static Discharge
Vibration:
Sinusoidal Vibration 8.0g for 72 hrs.
CERTIFICATION
UL:
UL listed
CSA:
CSA approved
PHYSICAL
Shipping Box:
12.50"
×
10.50"
×
9.75" (L
×
H
×
D)
318 mm
×
267 mm
×
248 mm (L
×
H
×
D)
Ship Weight:
14.25 lb. / 6.45 kg
Specifications subject to change without notice
Summary of Contents for SPM Series
Page 2: ......
Page 4: ......
Page 10: ...vi SPM Synchronous Motor Protection Control GE Power Management TABLE OF CONTENTS...
Page 74: ...6 4 SPM Synchronous Motor Protection Control GE Power Management 6 2 STATUS 6 ACTUAL VALUES 6...
Page 120: ...C 2 SPM Synchronous Motor Protection Control GE Power Management C 1 WARRANTY APPENDIXC C...
Page 124: ...iv SPM Synchronous Motor Protection Control GE Power Management INDEX...