GE Power Management
SPM Synchronous Motor Protection & Control
7-
11
7 TESTING AND TROUBLESHOOTING
7.5 PROGRAMMING
7
,
SCROLL DOWN key to move to REG PF set-point then SELECT/
ENTER to select the setpoint
,
Change the existing value of REG PF to 0.85 leading. SCROLL
Key(s) to select value of 0.85 and then SELECT/ENTER key to
accept new value
SCROLL DOWN key to move to REG GAIN setpoint. This setpoint
is correct
SCROLL DOWN key to move to STABILITY setpoint. This
setpoint is correct
,
SCROLL DOWN key to move to REG OUTPUT setpoint then
SELECT/ENTER to select the setpoint.
,
Change the existing value of REG PF to 10V. SCROLL Key(s) to
select value of 10 and then SELECT/ENTER key to accept new
value
,
SCROLL DOWN key to move to FLOOR VOLTS setpoint then
SELECT/ENTER to select the setpoint.
,
Change the existing value of FLOOR VOLTS to 5.00. SCROLL
Key(s) to select value of 5.00 and then SELECT/ENTER key to
accept new value
Exit out to SETPOINTS menu.
Save setpoint changes.
Exit out to PROGRAMMING MODE menu
Exit out to TEST MODE menu
Ready-mode display
Table 7–2: PROGRAMMING EXAMPLE (Sheet 4 of 4)
KEYPRESS
DISPLAY
COMMENTS
ENTER
REG PF:
OFF
ENTER to modify
ENTER
REG PF:
0.85
SCROLL to change
REG GAIN:
10
ENTER to modify
STABILITY: 1 cyc
ENTER to modify
ENTER
REG OUTPUT: 5 V
ENTER to modify
ENTER
REG OUTPUT: 10 V
SCROLL to change
ENTER
FLOOR VOLTS: 0.00
ENTER to modify
ENTER
FLOOR VOLTS: 5.00
SCROLL to change
SETPOINTS?
ENTER for menus
SAVE CHANGES?
ENTER to save...
ENTER
PROGRAMMING MODE
SCROLL PASSWORD
TEST MODE
SCROLL for tests
Coll-Ring Motor
SPM READY
Summary of Contents for SPM Series
Page 2: ......
Page 4: ......
Page 10: ...vi SPM Synchronous Motor Protection Control GE Power Management TABLE OF CONTENTS...
Page 74: ...6 4 SPM Synchronous Motor Protection Control GE Power Management 6 2 STATUS 6 ACTUAL VALUES 6...
Page 120: ...C 2 SPM Synchronous Motor Protection Control GE Power Management C 1 WARRANTY APPENDIXC C...
Page 124: ...iv SPM Synchronous Motor Protection Control GE Power Management INDEX...
Page 125: ...GE Power Management SPM Synchronous Motor Protection Control NOTES...