ZP3 Fire Control Panel Installation, Commissioning and Maintenance Manual
REV 11 (ISS 08/03/2010)
Page 49
Battery connection
This section describes how to connect the batteries to the power supply (see Figure 42). Make
sure that you comply with the “
General warnings and precautions”
on page xi and the
recommendations provided under “
Good practice
” on page 43.
Figure 42: Battery connection
Legend:
Item Description
Item Description
1
Battery connector socket
7
Battery connector lead
2 Plug
8 Connector
3 Red
9 Black
4
Black
10
230 VAC Types of cables: (a) spade lugs
(b) screw lugs
5 & 6
Grey
11
Red
Connection overview
Refer to Figure 42.
The batteries must be housed in their proper place.
The batteries must only be connected using the leads provided. These leads incorporate a
temperature-sensing element, used to provide temperature compensated charging.
The connector lead connects to the main board with a plug and socket. Battery positive is RED
(item 3), battery negative is BLACK (item 4), and the control leads are GREY (items 5 and 6).
Two final connector leads are provided - one for batteries with plug-in type connectors, the
other for batteries with screw connectors. Use the appropriate lead for your batteries.
The batteries must be connected in series with a jumper as shown in Figure 42.
Take care not to invert the battery connection polarity. If this happens, replace fuse F1 (6.3
Amp, slow-blow, 250V, size 20 mm x 5 mm).