Page 117
Menu functions
Edit disabled
Menu path
Maintenance/Edit disabled
Purpose
This menu allows you to group together all functions relating to enabling and disabling
points, zones and outputs.
Point
This option is used to enable or disable a point, accept the default point address displayed
or enter the address of the point to be edited. The point address and current state are
displayed. Use the scroll feature to display the next/previous point to be edited.
Zone
This option is used to enable or disable a zone, accept the default zone number displayed or
enter the zone number to be edited. The zone number and status will be displayed. Where
the points in a zone are not all set to any one status, the status is shown as "various
settings". Use the scroll feature to display the number of points in the zone and the totals of
enabled/disabled points within the zone.
Extinguish sys
This option is used to enable or disable Extinguishing Control Unit's. Only valid ECU
addresses are displayed. Use the scroll feature to select the ECU to edit.
Sounders
This option is used to enable or disable a sounder output. Only outputs and points declared
as sounders are displayed. Use the scroll feature to select the sounder to edit.
Note: Compliance with EN54-2 requires that ALL sounders are enabled / disabled together.
From Software version 3.11 onwards, this is achieved by pressing the Restore Disabled
Alarms button, which now toggles between Disable All Sounders and Enable All Sounders, as
indicated by the Sounders Disabled LED.
Outputs
This option is used to enable or disable an I/O mapped output, accept the default output
address displayed or enter the address of the output to be edited. The output address and
status are displayed. Use the scroll feature to display the output to be edited.
Remote alarm
This option is used to enable or disable the remote alarm relay (fire brigade) switched
outputs. Both the alarm and fault outputs may be edited in this menu.
View disabled
Menu path
Maintenance/View disabled
Purpose
This menu is used to view points, zones or outputs that have been disabled. A "extinguish
system" sub-menu is also provided to limit the points viewed to Extinguishing Control Units.
Once a sub-menu is chosen, the first disablement in the category is displayed. Use the scroll
feature to view the next/previous disablement..
Points
This option is used to display all points set to disabled.
Zones
This option is used to displays zones that are set to disabled. The zone number of the first
disabled zone and the number of points within the zone is displayed.
Extinguish sys
This option is used to display Extinguishing Control Units (ECU's) set to disabled.
Sounders
This option Is used to display sounders that are set to disabled.
Outputs
This option is used to display I/O mapping outputs set to disabled. The address of the first
disabled output is displayed. Use the scroll feature to view the next/previous disabled output.
Remote alarm
This option is used to view the enabled/disabled status of the remote alarm relay (fire
brigade) switched outputs. Both the alarm and fault outputs may be viewed in this menu.