Table 32: Device definition table and device type analogues interpretation
Model
Description
Code
Reading 1
Reading 2
Reading 3
ZP710-2
Analogue ionization sensor
212
197-226 (213)
228-255 (245) 197-226 (213)
ZP720-2
Analogue heat sensor
213
197-226 (213)
228-255 (245) 165-194 (180)
ZP720-3
Analogue heat sesnor
217
197-226 (213)
228-255 (245) 039-068 (054)
ZP725-2
Analogue heat sensor –with rate of rise
element
214
197-226 (213)
228-255 (245) 133-162 (152)
ZP730-2
Analogue optical sensor
215
197-226 (213)
228-255 (245) 102-131 (118)
ZP732-2
Analogue duet sensor (optical/heat)
216
197-226 (213)
228-255 (245) 070-100 (084)
ZP5-IF8-22
8 way interface fire callpoint board
222
197-226 (213)
197-226 (213) 197-226 (213)
ZP5-IF8-23
8 way interface fire sprinkler board
223
197-226 (213)
197-226 (213) 165-194 (180)
ZP740-2-23
Analogue interface fire sprinkler
223
197-226 (213)
197-226 (213) 165-194 (180)
ZP5-IF8-24
8 way interface fire general purpose
board
224
197-226 (213)
197-226 (213) 133-162 (152)
ZP740-2-24
Analogue interface fire general purpose 224
197-226 (213)
197-226 (213) 133-162 (152)
ZP745
Interface unit
224
197-226 (213)
197-226 (213) 133-162 (152)
A45E
Interface unit
224
197-226 (213)
197-226 (213) 133-162 (152)
ZP740ST
Analogue interface for high sensitive
smoke detector (stratos)
233
197-226 (213)
165-194 (180) 165-194 (180)
ZLS1APIC Analogue
interface for high sensitive
smoke detector (stratos)
233
197-226 (213)
165-194 (180) 165-194 (180)
ZP755
Loop sounder (all variants)
241
197-226 (213)
133-162 (152) 228-255 (245)
ZP750-2
Line relay
242
197-226 (213)
133-162 (152) 197-226 (213)
A50E
Line relay
242
197-226 (213)
133-162 (152) 197-226 (213)
A51E
High voltage line relay
242
197-226 (213)
133-162 (152) 197-226 (213)
ZP752-2
Dual line sounder unit
245
197-226 (213)
133-162 (152) 102-131 (118)
ZP753-2
Addressable LED indicator
246
197-226 (213)
133-162 (152) 070-100 (084)
ZP754*-2
Addressable line sounder
247
197-226 (213)
133-162 (152) 039-068 (054)
ZP755
Loop sounder (ZP754 mode)
247
197-226 (213)
133-162 (152) 039-068 (054)
ZP5-IF8-52
8 way interface fire non-fire/auxiliary
board
252
197-226 (213)
102-131 (118) 197-226 (213)
ZP740-2-52
Analogue interface non-fire/auxiliary
252
197-226 (213)
102-131 (118) 197-226 (213)
ZP5-IF8-53
8 way interface fire non-alarm/control
board
253
197-226 (213)
102-131 (118) 165-194 (180)
ZP740-2-53
Analogue interface non-alarm/control
253
197-226 (213)
102-131 (118) 165-194 (180)
ZP5-IF8-54
8 way interface fire non-alarm/control
board
254
197-226 (213)
102-131 (118) 133-162 (152)
ZP740-2-54
Analogue interface non-alarm/control
254
197-226 (213)
102-131 (118) 133-162 (152)
ZP5-IF8-62
8 way interface fire security latching
board
262
197-226 (213)
070-100 (084) 197-226 (213)
ZP740-2-62
Analogue interface security latching
262
197-226 (213)
070-100 (084) 197-226 (213)
ZP5-IF8-64
8 way interface fire security non-
latching board
264
197-226 (213)
070-100 (084) 133-162 (152)