ZP3 Fire Control Panel Installation, Commissioning and Maintenance Manual
REV 11 (ISS 08/03/2010)
Page 41
Flush mounting
The ZP3 panel protrudes by only 10 mm when flush mounted. Two types of flush mounting kits
are available, as shown and described in Figure 34. Both use the same collar, and look the same
when installed.
Figure 34: Flush mounting
Flush mounting Collar
(without Backbox)
In this variation, the panel backbox is fitted
into the wall cavity, with careful alignment. It is
then conduited and wired. The flushing collar is
then fitted to aesthetically complete the
installation.
Flush mounting Collar (with Backbox)
In this variation, a special flushing-backbox is fitted into the wall
cavity, and all conduit and cables are brought into this box, and
terminated on terminals. This box therefore forms both a
recessed tray and terminal box. The ZP3 panel and flushing collar
are then fitted into the recessed tray. The advantage of this
system is that the wall cavity recessed box can be roughly
installed, and out of alignment. The system allows the panel and
collar to be perfectly aligned after installation.
Legend:
Item Description
Item Description
1
Flush mounted ZP3 panel
5
ZP3 panel backbox
2 Flush
collar
6 Terminals
3
ZP3 panel backbox
7
Flushing box
4 Flush
collar