ZP3 Fire Control Panel Installation, Commissioning and Maintenance Manual
Page 126
REV 11 (ISS 08/03/2010)
Extinguishing control unit
The Extinguishing control unit in particular makes extensive use of slots 5 and 6 to indicate status.
These analogues are shown in Table 35 for slot 5 and Table 36 for slot 6.
Table 35: Extinguishing control unit – slot 5 (address 1)
Details Nominal
value
Digital counts
Normal idle value
39 - 65
Manual when door locked
68-100
Loss of signal <
39
General panel fault
103 – 132
Power supply fault
> 163
Relay operated 141
– 163
Table 36: Extinguishing control unit – slot 6 (address 1)
Details Nominal
value
Digital counts
Fault – low idle
< 39
Auto released
39 – 65
Manual released
68 – 100
System locked-off (released)
103 – 132
Auto non-released
141 –163
System locked-off (non-released)
166 – 195
Manual (non-released)
> 198