ZP3 Fire Control Panel Installation, Commissioning and Maintenance Manual
REV 11 (ISS 08/03/2010)
Page 89
EN54 Setup requirements
Summary
The setup requirements to conform to EN54 are provided below. All paragraph numbers refer to
EN54 part 2 of 1997 unless otherwise specified.
1. Para 7.1.4 & 8.1.3 - AVF shall be switched off for all points.
2. Para 7.3.1 - Under menu \setup\system configuration\zone LED link, zone LEDs shall be linked
to the appropriate zones.
3. In menu \setup\system configuration\control keyswitch level:
Para 7.4.1
The "accept" key shall be set up to level 1 or 2
Para 7.6.1
The "reset" key shall be set up to level 2
Para 7.8(a)
The "silence alarms" key shall be set up to level 2
Para 7.8(b)
The "sound alarms" key shall be set up to access level 2
4. Para 7.8 - If accessory board ZP3AB-MA8 outputs are required to serve the function of "output
to fire alarm devices (item C)" then they must be defined as "sounder outputs" when mapping.
"Standard outputs" and use of non-monitored output boards shall not be used to comply with
EN54 item C requirements.
5. Para 7.10 - If accessory board ZP3AB-MA8 outputs are required to serve the function of
"control to fire protection equipment" then they must be defined as "control outputs" when
mapping. The programming must not include delays to output when the output is used to
serve the function of "control to fire protection equipment." "Standard outputs" and use of
non-monitored input/output boards shall not be used to comply with EN54 item G
requirements.
6. Para 7.11(a) - Under menu \setup\system configuration\relays\sounder relays, the sounder
relays must be defined as "programmable". The relays must then be mapped as outputs
(addresses 09-173 and 09-178) using the I/O mapping function. They must defined as
"sounder outputs", silencing with no delay.
Note:
A suitable input would be the common fire LED at address 09-129).
7. Para 7.11(c) - The day delay and more time extension shall be set to a maximum of 10
minutes as it automatically affects the delay to RMC alarm output.
8. Para 7.11(c) - The I/O mapping to common sounder outputs (addresses 09-173 and 09-178)
shall be set to a maximum delay of 10 minutes (including day delay and more time extension
if operating in day mode).
9. Para 7.11(d) - Under menu \setup\system configuration\panel options\day delay override set
up so that callpoints do override the day delay.
10. Para 7.12 - To meet co-incidence detection requirements either:
(a) Use the coincidence function in the setup/zoning menu to inhibit the indication of fire
alarm condition (first alarm in will show as a pre-alarm) OR (b) Facilitate option to inhibit fire
alarm devices and fire protection equipment by mapping each appropriate output double
knock from the zone.
11. Para 8.2.4(c) - Earth fault monitoring shall be enabled (by inserting link J1 on the Main Control
Board).
12. Para 8.2.5/6 - The auxiliary 24 Volt power supply output shall not be used to drive
unmonitored equipment i.e. equipment which will not automatically notify a fault to the
control panel should loss of power occur. Line units such as ZP752-2 are monitored.