ZP3 Fire Control Panel Installation, Commissioning and Maintenance Manual
Page 124
REV 11 (ISS 08/03/2010)
The panel interprets the reading according to the device type. The panel uses sophisticated
algorithms based on these readings and their change over time to determine the true conditions
in the area covered by the device. Viewing a snapshot of the analogue readings cannot provide
information with the same degree of accuracy; nevertheless values can be interpreted, as in the
following tables, in order to help assess the status of a device.
Analogue status – idle limits
The resting values of the analogues when devices are in normal conditions are provided in Table
33. The resting value is referred to as the idle value and can take on any values in the ranges
given below, usually this will be near the mid-point of the range.
Table 33: Analogue status – idle limits
Model 1
High
2
Standard
3
Medium
4
Low
ZP710-2
20-108 20-108 20-108 20-108
ZP720-2
25-123 25-143 25-186 25-186
ZP725-2
25-123 25-151 25-174 25-194
ZP730-2
20-108 20-108 20-108 20-108
ZP732-2
optic
20-108 20-108 20-108 20-108
ZP732-2
heat
25–163 25–163 25–179 25–179
ZP720-3
25-123 25-163 25-179 25-179
ZP740-2
59-137 59-137 59-137 59-137
ZP745 59-137 59-137 59-137 59-137
ZP770-2
59-137 59-137 59-137 59-137
ZP740ST
39-104 39-104 39-104 39-104
ZP755 40-110 40-110 40-110 40-110
ZP750-2
59-140 59-140 59-140 59-140
ZP752-2
40-140 40-140 40-140 40-140
ZP753-2
40-110 40-110 40-110 40-110
ZP754*-2
40-110 40-110 40-110 40-110
ZP5-IF8
59-137 59-137 59-137 59-137
ZX832-2
optic
20-100 20-100 20-100 20-100
ZX832–2
heat
25–164 25–164 25–179 25–179
ZR420
85 85 85 85
ZR430
85 85 85 85
Radio
Sounder
85 85 85 85
ZP710Ex-1
10-54 10-54 10-54 10-54
ZP720Ex-1
12-71 12-71 12-93 12-100
ZP785-3
59-137 59-137 59-137 59-137
ZP786Ex-1
29-58 29-58 29-58 29-58
ZP740Ex-1
29-58 29-58 29-58 29-58
ZP5-570-2
59-137 59-137 59-137 59-137
ZP5-574
59-137 59-137 59-137 59-137